Remak VCS Installation And Operating Instructions Manual page 79

Table of Contents

Advertisement

Connection to the Master System (ModBus Standard)
Input states (Read) (continuation)
Adress
Description
1x0027
Supply fan alarm
1x0028
Supply fan fdbk
1x0029
Sply fan deviation
1x0030
Exhaust fan alarm
1x0031
Exhaust fan fdbk
1x0032
Exhaust fan deviation
1x0033
Fan op hours alarm
1x0036
Cooling DX alarm
1x0037
1x0038
Cooling pump alarm
1x0039
Ice build-up on the heat pump evaporator
1x0040
Heat recovery alarm
1x0041
1x0042
1x0043
Hrec frost monitor
1x0044
1x0045
Htg pump alarm
1x0046
1x0047
Htg frost monitor
1x0048
El htg alarm
1x0049
Heat pump blocking by outdoor temperature
1x0050
Heat pump blocking by pressure in the plate
heat-exchanger
1x0051
Heat pump operation blocking
1x0052
1x0053
1x0054
1x0055
1x0056
El heating 2 alarm
1x0057
Sply tmp deviation
1x0058
Room tmp deviation
1x0059
1x0062
1x0063
Control units VCS
Values/Units
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
Remarks
OK*Alarm
OK*Alarm
Passive*Active
OK*Alarm
OK*Alarm
Passive*Active
Passive*Active
OK*Alarm
OK*Alarm
OK*Alarm
OK*Alarm
OK*Alarm
OK*Alarm
OK*Frost
OK*Alarm
Passive*Active
Passive*Active
OK*Alarm
OK*Alarm
Passive*Active
Passive*Active
77