Remak VCS Installation And Operating Instructions Manual page 45

Table of Contents

Advertisement

Parameter
Notation
Reading
code
level
code
level
898
A
898 A
Displayed time format - 12h/24h
Passwords
899
S
899 S
Password for Service level access
901
A
901 A
Password for Admin level access
902
U
902 U
Password for User level access
903
G
903 G
Password for Guest level access
Comunication with Building management system
(BMS) - (After settings - reset required !!)
LON
921
S
921 S
Send heart beat (s)
922
S
922 S
Receive heart beat (s)
923
S
923 S
Min send intervall (s)
924
S
924 S
Service pin
925
S
925 S
Out temperature value
926
S
926 S
Fire alarm (external)
Modbus RTU - Slave (BMS)
925
S
925 S
Out temperature value
926
S
926 S
Fire alarm (external)
931
S
931 S
Modbud Slave1
932
S
932 S
Address Slave1
933
S
933 S
Baud rate Slave1
2400 (factor 10)
4800 (factor 10)
9600 (factor 10)
19200 (factor 10)
38400 (factor 10)
934
S
934 S
Stop bits Slave1
935
S
935 S
Parity Slave1
936
S
936 S
Termination (resistor) Slave1
937
S
937 S
Response timeout Slave1
Control units VCS
Menu HMI-SG
Meaning
0 24 h
1 12 h
0 inactive
1 active
0 of application
1 of communication
0 of application
1 of communication
0 of application
1 of communication
0 of application
1 of communication
0 inactive
1 active
default
0 One stop bit
1 Two stop bits
0 Even
1 Odd
2 None
0 inactive
1 active
Factory Settings
Value
Min
Max
0
9999
0
9999
0
9999
0
9999
2700
0
9999
s
3600
0
9999
s
5
0
9999
s
0
0
1
9600
b/s
1
2
0
5
0
3600
s
43