Electronic Expansion Valve Overheating Controller EC3-X33

Safety Instructions
Read these Operating Instructions carefully. Incorrect use can
result in serious damage to the device and personal injury.
Installation can only be performed by a suitably qualifi ed and
experienced person.
Before starting the installation, all power supply sources must
be disconnected.
Temperatures must be within the specifi ed ranges.
All connections must comply with the applicable electrical
regulations in force.
Th e device must not be connected to voltage until all electrical
connections have been connected.
Warning: Th e EC3-X33 controller is equipped with a renew-
able backup source containing lead and acids. Th erefore, it
cannot be disposed along with normal waste – the battery
is subject to waste recycling regulations. In any case, it must
be recycled in accordance with the applicable regulations in
force (98/101/EEC).
Technical Data
Power supply
Energy consumption
Terminal box
Grounding
Degree of protection
Connection to ECD-002
Digital Input I
NTC input
Inlet pressure input, 4-20mA
Output 4-20mA
Deviation from the input signal
Failure relay H
104
If the output relay is not used, the user must ensure
proper safety regarding power supply breakdown-related
failures.
Output for EX4
to 8 valves
Teplota okolí
To keep the system reliable, it is advisable to change
the battery every year.
Location
Th e EC3-X33 controller can be installed on the DIN bar. Th e
EC3-331 controller is designed to be installed on the DIN bar.
Position: On a vertical plate with the output for the step motor
situated only on the upper side.
Electrical Connection
Zapojení podle schématu
Th e device may only be connected to the power supply once
all conductors have been connected in accordance with the
wiring diagram.
Th e device cover is grounded to the 6.3 mm terminal.
Warning: To comply with the applicable regulations (especially
CEI 107-70), it is necessary to ensure the following: T trans-
former 24 V AC must be double insulated in Class II. Power
supply 24 V AC is not grounded. To eliminate mutual infl uence
and grounding problems, it is recommended to use separate
condensers for the EC3 and other devices. If connected to
the mains, the EC3 will be destroyed.
24 VAC ±10%, 50/60 Hz Class II
25 VA max. EC3-X32, incl. EX 4-8
Push-in type for 0.14 ... 1.5 mm2 conductors
6.3 mm grounding connector
IP20
ECC-N** or category 5 conductor with RJ45
0 / 24V DC/AC for ON/OFF control
ECN-N60, output temperatures from the evaporator
PT5/07M;PT5/18M;PT5/30M Alco Controls
for other controller K 12/24V
Max. ± 8%
SPDT 24 V DC/AC 2 A ind
ON
Failure-free operation
OFF
Failure or disconnected power supply
at 24 V DC, max. 0.8 A
0...60 °C
1...25 °C (the longest
battery service life)
> 35 °C (battery service
life < 2 years)