Connection to the Master System (ModBus Standard)
Input states (Read) (continuation)
Adress
Description
1x0101
1x0102
RmUTmp1
1x0103
RmUTmp2
1x0104
BrnrFlueTmp
1x0105
PreElHtgTmp
Input register (Read)
Adress
Description
1x0106
PreEtrHtgTmp
3x0001
General status (Word 1)
Bit0
Alarm class danger (A)
Bit1
Alarm class critical (A)
Bit2
Alarm class low (B)
Bit3
Alarm class warning (B)
Bit4
Bit5
Bit6
Bit7
Bit8
Bit9
Bit10
Bit11
Actual control temp, room
Bit12
Actual control temp, exh
Bit13
Actual control temp, sply
Bit14
Bit15
3x0005
Digital inputs (Word 1)
Bit0
Bit1
External control 1
Bit2
External control 2
Bit3
Bit4
Bit5
Control units VCS
Values/Units
°C
°C
°C
°C
Values/Units
°C
0-65535
0-65535
Remarks
OK*Alarm
OK*Alarm
OK*Alarm
OK*Alarm
Remarks
OK*Alarm
Unsigned Word
0-1 for each bit or counted binary
to a decimal number
Unsigned Word
0-1 for each bit or counted binary
to a decimal number