List of Data Points (HMI-SG controller)
Parameter
Notation
Reading
code
level
code
level
185
A
185 A
For operating stage St2
186
A
186 A
For operating stage St3
187
A
187 A
For operating stage St4
188
A
188 A
For operating stage St5
TRN – fan start-up (without outlet for dampers)
189
S
189 S
Forced fan start-up time setting to Stage 1
Two-speed motors
190
A
191 U
Transition time interval from speed 1 to speed 2
192
A
193 U
Transition time-out from speed 2 to speed 1
Inlet temperature limitation
194
S
194 S
Minimum inlet air temperature
195
S
195 S
Maximum inlet air temperature
Additional operating modes, functions
196
S
196 S
Outdoor temperature dependent fan speed compensation
197
S
197 S
Heating/cooling dependent fan speed compensation
32
Menu HMI-SG
Meaning
5
+ 1 stage
6
+ 2 stages
7
+ 3 stages
8
+ 4 stages
0
- 4 stage
1
- 3 stage
2
- 2 stage
3
- 1 stage
4 0
5
+ 1 stage
6
+ 2 stages
7
+ 3 stages
8
+ 4 stages
0
- 4 stage
1
- 3 stage
2
- 2 stage
3
- 1 stage
4 0
5
+ 1 stage
6
+ 2 stages
7
+ 3 stages
8
+ 4 stages
0
- 4 stage
1
- 3 stage
2
- 2 stage
3
- 1 stage
4 0
5
+ 1 stage
6
+ 2 stages
7
+ 3 stages
8
+ 4 stages
0
- 4 stage
1
- 3 stage
2
- 2 stage
3
- 1 stage
4 0
5
+ 1 stage
6
+ 2 stages
7
+ 3 stages
8
+ 4 stages
0 No
1 Yes
0 No
1 Heating
2 Cooling
Factory Settings
Value
Min
Max
0
0
0
0
20
0
99
s
15
0
999
s
12
0
99
s
15
0
64
°C
35
0
64
°C
0
0