List of Data Points (HMI-SG controller)
Parameter
Notation
Reading
code
level
code
level
339
A
340 U
Cooling end point (outdoor temperature)
341
A
342 U
Maximum cooling compensation (speed)
343
A
344 U
Heating initial point (outdoor temperature)
345
A
346 U
Heating end point (outdoor temperature)
347
A
348 U
Maximum heating compensation (speed)
349 U
Current cooling speed compensation
350 U
Current heating speed compensation
Room (outlet) temperature dependent fan speed compensation
351
A
351 A
Compensation function setting
352 U
Actual compensation
353
A
353 A
Required room temperature
Heating/cooling dependent fan speed compensation
354
A
354 A
Heating temperature hysteresis
355
A
355 A
Cooling temperature hysteresis
356 U
Heating compensation display
357 U
Cooling compensation display
Air quality dependent compensation (damper position/fan speed)
358
A
359 U
Compensation function setting (according to the sensor characteristics)
360
A
361 U
Required (allowable) value of the CO2, VOC, (CO) concentration
362
A
363 U
CO2, VOC, (CO) sensor range setting
364 U
CO2, VOC (CO) compensation rate display
Sequence
Heat pump - heating
365
A
366 U
Outdoor temperature dependent heat pump blocking
Temp. hysteresis applied for outdoor temperature dependent heat pump
367
A
368 U
unblocking
369
A
370 U
Minimum operating time for heat pump heating
371
A
372 U
Re-heating blocking
373
A
374 U
Heat pump switching on
375
A
376 U
Digital output opening hysteresis
377 U
Information - outdoor temperature dependent heat pump heating blocking 0 inactive
Heat pump - cooling
378
A
379 U
Outdoor temperature dependent heat pump blocking
Tep. hysteresis applied for outdoor temperature dependent heat pump
380
A
381 U
unblocking
382
A
383 U
Minimum operating time for heat pump cooling
384
A
385 U
Re-cooling blocking
386
A
387 U
Heat pump switching on
388
A
389 U
Digital output opening hysteresis
390
A
391 U
Heat pump low reference signal setting for A output
392 U
Information - outdoor temperature dependent heat pump cooling blocking 0 inactive
Heat Pump - Special
260 S
Inversion signal for Heat Pump – heating
261 S
Inversion signal for Heat Pump – cooling
262 S
Special signal 0-10V (Daikin) switchover
263 S
The difference between the demand and the real signal to determine St2
264 S
Time needed to pass from 0 to 100%
265 S
The signal voltage request of heating (Toshiba)
266 S
The signal voltage request of cooling (Toshiba)
267 S
The signal voltage request of STOP (Toshiba)
36
Menu HMI-SG
Meaning
0 increase
1 decrease
0 Normal
1 Inverted
1 active
1 active
0 Off
1 On
0 Off
1 On
0 Off
1 On
Factory Settings
Value
Min
Max
30
-64
64
°C
0
-100 100
%
5
-64
64
°C
-20
-64
64
°C
0
-100 100
%
-100 100
%
-100 100
%
0
0
100
%
20
0
99
°C
1
0
20
°C
1
0
20
°C
0
100
%
0
100
%
0
800(50)
0
3000
ppm
2000(300)
0
3000
ppm
0
100
%
-8
-45
35
°C
3
1
10
°C
60
0
9999
s
120
5
600
s
20
0
100
%
10
1
100
%
14
-45
35
°C
3
1
10
°C
60
0
9999
s
120
5
600
s
20
0
100
%
10
1
100
%
30
0
50
%
40
0
100
%
120
0
500
s
3.25
0
10
V
6.25
0
10
V
0
0
10
V