List of Data Points (HMI-SG controller)
Parameter
Notation
Reading
code
level
code
level
216
A
216 A
Control signal 0-10 V or 2-10 V, heat exchanger by-pass damper
217
A
217 A
Control signal 0-10 V or 2-10 V, chamber by-pass damper
Required inlet temperature extra set-point
Required inlet temperature extra set-point (applied when el. re-heating or
218
A
219 G
heat pump is removed from the main sequence)
220
S
220 S
Fan start-up delay (after damper)
Outdoor-dependent fan speed interlocking
221
S
221 S
Control – Flow (Pressure)
222
A
223 U
Setting range of flow sensor - inlet (a factor of 100)
224
A
225 U
Setting range of flow sensor - outlet (a factor of 100)
226
A
227 U
Setting range of pressure sensor - inlet (a factor of 100)
228
A
229 U
Setting range of pressure sensor - outlet (a factor of 100)
232
A
233 U
K factor – inlet
234
A
235 U
K factor – outlet
236
A
237 U
NunberInletFan
238
A
239 U
NunberOutletFan
240 S
K Factor - Enabled
Inputs configuration
241 S
Reverse function of fault input for Cooling or Heat Pump
Device configuration
270 U
Regulation supply fan
271 U
Regulation exhaust fan
272 U
Regulation additional fan
273 U
Heating
34
Menu HMI-SG
Meaning
0 0-10V
1 2-10V
0 0-10V
1 2-10V
0 No
1 Yes
0 Normal
1 Reversed
0 none
1 1 stage
2 5 stage (TRN)
3 V10
4 V100
5 V10 + back-up
6 V100 + back-up
7 2xV10
8 2xV100
9 2xV10 + back-up
10 2xV100 + back-up
0 none
1 1 stage
2 5 stage (TRN)
3 V10
4 V100
5 V10 + back-up
6 V100 + back-up
7 2xV10
8 2xV100
9 2xV10 + back-up
10 2xV100 + back-up
0 none
1 1 stage
2 5 stage (TRN)
3 V10
4 V100
7 2xV10
8 2xV100
0 no
1 water
2 electric
3 gas
Factory Settings
Value
Min
Max
1
1
20
0
99
°C
20
0
9999
s
-60
-64
64
°C
8000
0
2*105
m3/h
8000
0
2*105
m3/h
6000
0
7000
Pa
6000
0
7000
Pa
95
0
9999
95
0
9999
1
1
100
1
1
100
1
0