Connection to the Master System (ModBus Standard)
Description of Pre-defined Variables in the Modbus Network
This section includes a description of variables (registers) according to the assigned REMAK data points. The list below includes
specifications of variables for different VCS control system variants at the discretion of REMAK a.s.
For example, if the VCS control system (air-handling device) has not been equipped with gas heating, it will not be possible to
use these variables.
Coil status (Read/Write)
Adress
Description
0x0001
Alarm acknowledge
0x0002
0x0003
0x0004
0x0007
0x0011
0x0012
Ext control input 1
0x0013
Ext control input 2
0x0014
0x0015
Fire alarm
Input states (Read)
Adress
Description
1x0001
Alarm class danger (A)
1x0002
Alarm class critical (A)
1x0003
Alarm class low (B)
1x0004
Alarm class warning (B)
1x0005
1x0011
1x0012
Ext control input 1
1x0013
Ext control input 2
1x0014
1x0015
1x0020
1x0021
1x0022
1x0023
1x0024
1x0026
Fan alarm
76
Values/Units
0-1
0-1
0-1
0-1
Values/Units
0-1
0-1
0-1
0-1
0-1
0-1
0-1
Remarks
Off*On
Off*On
Off*On
OK*Alarm
Remarks
Off*On
Normal*Alarm
Normal*Alarm
Normal*Alarm
Off*On
Off*On
OK*Alarm