Remak VCS Installation And Operating Instructions Manual page 43

Table of Contents

Advertisement

Parameter
Notation
Reading
code
level
code
level
770 S
771 A
Derivative factor
Difference between required and inlet temperature monitoring
801
A
802 G
Maximum difference (±°C)
803
A
804 G
Minimum limit (°C)
805
A
806 G
Time delay after AHU start-up (s)
Difference between required and room (outlet) temperature monitoring
807
A
808 G
Maximum difference (±°C)
809
A
810 G
Minimum limit (°C)
811
A
812 G
Time delay after AHU start-up (s)
Remote fault
813
A
814 G
Failure class selection to digital output
815 G
Alarm message (generated depending on priorities)
Fire mode
816
A
817 G
Fan behaviour during fire selection
818
A
819 G
Fan output during fire selection
820
A
821 G
Fire alarm activation inlet temperature
822
A
823 G
Fire alarm activation outlet temperature
Alarm number for HMI
824 U
Alarm number
System settings - control unit
825
A
825 A
Failure acknowledgement (reset of all failures after they have been removed) 0 No
826
S
826 S
Software reset of the controller
827
S
827 S
Control unit location building physical address
828
S
828 S
Control unit location floor physical address
829
S
829 S
Control unit device address
SD card
830
S
Application load from SD card
834
S
Parameter save to SD card
835 S
Parameter save to SD card - successful
836
S
Parameter load from SD card
837 S
Parameter load SD card - successful
831
S
831 S
Data point recovery (factory settings)
User settings
832
A
832 A
Data point saving (user settings)
833
A
833 A
Data point recovery (user settings)
ModBus
838 S
Alarm
839
S
839 S
Failure flow activation delay (at fan start-up)
840
S
840 S
Failure flow activation delay (during fan run)
841
S
841 S
Thermo-contact (TK) failure activation delay (fans)
842
S
842 S
Frequency inverter failure activation delay
Control units VCS
Menu HMI-SG
Meaning
0 Failure A
1 Failure A+B
0 Normal
1 Alarm
0 Stop
1 Inlet fan
2 Outlet fan
3 Both fans
1 Yes
0 without reset
1 reset
0 No change
1 Loading
0 Passive
1 Active
0 No
1 Yes
0 Passive
1 Pasrtial
2 Full
0 No
1 Yes
0 No
1 Yes
0 without saving
1 with saving
0 No
1 Yes
0 OK
1 Error
Factory Settings
Value
Min
Max
0
s
10
0
99
°C
10
0
99
°C
60
0
9999
s
10
0
99
°C
10
0
99
°C
600
0
9999
s
1
0
80
0
100
%
70
0
99
°C
50
0
99
°C
0
0
15
0
0
15
0
0
250
45
0
600
s
5
0
600
s
2
0
600
s
2
0
600
s
41