List of Data Points (HMI-DM, HMI-TM and HMI@WEB controllers)
ActiveMaxFrshAirDHrec
Apply + Reset
HMI-SG
DisplayedRoomTemp
SetpoitRangeCorr
SetpointIncrement
TimeFormat
External Control
ToggFuncInp1
DelayOfTmToAUTO
FanOutputStg1
FanOutputStg2
TmpMod1
TmpMod2
FanStageExtCnt
Identification device
Name of device
Number of devices
Location of the
installation
Checks
Save / Restore
UpgradeStart
SaveDataOnSDCard
SaveDataFromSDCard
RestoreFactorySetting
Restore settings
Save settings
Operating hours
Supply fan
Exhaust fan
Additional fan
Operating hours
settings fans
Water preheating
ElectricPreheating
Heating water
Electrical heating
Cooling water
CoolingCondenUnit
ChlazKondJednotka 2
ChlazKondJednotka 3
ExtraElectricalHtg
TepČerpadlo-ohřev
TepČerpadlo-chlaz
TepČerpadlo2-ohřev
TepČerpadlo2-chlaz
TepČerpadlo3-ohřev
TepČerpadlo3-chlaz
SetpointAndSupplyTmpDeviation
MaxDeviation
MinLimit
DlyOnTmEvalAfterStart
SetpointAndRoomTmpDeviation
MaxDeviation
MinLimit
DlyOnTmEvalAfterStart
FireAlarmActivityFans
FireAlarmFansOutSpv
SplyTmpFireLmt
ExhstTmpFireLmt
Connection
Modbus Master
AdrFreqInv1SplyFan
AdrFreqInv2SplyFan
AdrFreqInv3SplyFan
AdrFreqInv4SplyFan
AdrFreqInv5ExhFan
AdrFreqinv6ExhFan
AdrFreqInv7ExhFan
AdrFreqInv8ExhFan
AdrFreqInv9AddFirst
AdrFreqInv10AddSec
AdrFreqInv11RotHeatExch
ResistiveTerminatBus
NumberRepeatErrMess
NumberOfErrMess
LAN Connection
DHCP
ActIPAdr
ActMaskAdr
66
OperationHoursAlm
EnblOperHoursAlm
OperHoursLimit
Function activation - Max. limit of fresh air ac-
cording to T outdoor (vent. unit)
Reset after configuration of additional modes/functions
HMI-SG
Room temperature display, combined or inlet temperature
Required value compensation setting +/-
Required temperature increment setting (0.5/0.1) (°C)
Displayed time format (12h/24h)
External control
External contact function definition (Ext. control 1 contact)
Transition time from ext. control mode to AUTO mode (Ext. control 1 contact)
Fan output stage setting (Ext. control 1 contact or 2 contacts)
Fan output stage setting "Higher" (Ext. control 2 contacts)
Temperature mode setting (Ext. control 1 contact or 2 contacts)
Temperature mode setting "Higher" (Ext. control 2 contacts)
Fan output stages (external control)
Device identification
Equipment name
Device number
Device location
Checks
Saving and recovery
Application loading from SD card
Data saving to SD card
Data loading from SD card
Factory settings recovery
Settings recovery
Save settings
Operating hours
Operating hour counter - inlet fan
Operating hour counter - outlet fan
Operating hour counter – 3rd auxiliary fan
Fan operating hours settings
Fan operating hour alarm state
Alarm enable fan operating hour
Operating hours for alarm activation
Operating hour counter – water pre-heating
Operating hour counter - electric pre-heating
Operating hour counter - water heating
Operating hour counter - electric heating
Operating hour counter - water cooling
Operating hour counter – condensing unit
Operating hour counter – condensing unit 2
Operating hour counter – condensing unit 3
Operating hour counter - electric after-heating
Operating hour counter – Heating Pump - heating
Operating hour counter – Heating Pump - cooling
Operating hour counter – Heating Pump 2 - heating
Operating hour counter – Heating Pump 2 - cooling
Operating hour counter – Heating Pump 3 - heating
Operating hour counter – Heating Pump 3 - cooling
Difference between required and inlet air temperature monitoring.
Maximum difference (±°C)
Minimum limit (°C)
Time delay evaluation after AHU start-up (s)
Difference between required and room (outlet) air temperature monitoring.
Maximum difference (±°C)
Minimum limit (°C)
Time delay evaluation after AHU start-up (s)
Fan behaviour during fire alarm
Fan output during fire alarm
Fire alarm activation inlet temperature
Fire alarm activation outlet temperature
Connection
ModbusMaster
Frequency inverter 1 address, inlet fan
Frequency inverter 2 address, inlet fan backup or second inlet fan
Frequency inverter 3 address, inlet fan twin backup
Frequency inverter 4 address, inlet fan twin backup
Frequency inverter 5 address, outlet fan
Frequency inverter 6 address, outlet fan backup or second outlet fan
Frequency inverter 7 address, outlet fan twin backup
Frequency inverter 8 address, outlet fan twin backup
Frequency inverter 9 address, 3rd auxiliary fan
Frequency inverter 10 address, second 3rd auxiliary fan
Frequency inverter 11 address, rotary heat exchanger
Control unit Modbus resistance terminal
Number of message repeating during error transfers
Number of error transfers for communication failure evaluation
LAN connection
DHCP
Current IP address
Current mask address
3
0
12
°C
0.1
0.1
0.5
°C
24
12
24
h
0
0
23
h
17520
0
h
999999
10
0
99
°C
10
0
99
°C
60
0
9999
s
10
0
99
°C
10
0
99
°C
600
0
9999
s
80
0
100
%
70
0
99
°C
50
0
99
°C
1
2
3
4
5
6
7
8
9
10
11
2
6