List of Data Points (HMI-DM, HMI-TM and HMI@WEB controllers)
GasHeatingMaximalTempFlueGas
GasHeatingMinimumTempFlueGas
Electrical preheting
Extra electrical heating
Heat pump - heating
Heat pump - cooling
Heat pump 2 - heating
Heat pump 2 - cooling
Heat pump 3 - heating
Heat pump 3 - cooling
Heat recovery
Heat exchanger freeze
Mixing
Cooling
Humidification
Dehumidity
Humidity cascade
FanCompensationSequenceHtg
FanCompensationSequenceClg
FanCompensationRoomExhaustTmp
FanCompensationHumidity
64
Menu HMI-DM,HMI-TM a HMI@WEB
Menu
PropFactor
IntegFactor
DifferFactor
PropFactor
IntegFactor
DifferFactor
PropFactor
IntegFactor
DifferFactor
PropFactor
IntegFactor
DifferFactor
PropFactor
IntegFactor
DifferFactor
PropFactor
IntegFactor
DifferFactor
PropFactor
IntegFactor
DifferFactor
PropFactor
IntegFactor
DifferFactor
PropFactor
IntegFactor
DifferFactor
PropFactor
IntegFactor
DifferFactor
PropFactor
IntegFactor
DifferFactor
PropFactor
IntegFactor
DifferFactor
PropFactor
IntegFactor
DifferFactor
PropFactor
IntegFactor
DifferFactor
PropFactor
IntegFactor
DifferFactor
PropFactor
IntegFactor
DifferFactor
PropFactor
IntegFactor
PropFactor
IntegFactor
DifferFactor
PropFactor
IntegFactor
DifferFactor
PropFactor
IntegFactor
DifferFactor
Meaning
Maximum temperature of flue gas
Proportional factor
Integrating factor
Derivative factor
Minium temperature of flue gas
Proportional factor
Integrating factor
Derivative factor
Electric pre-heating factors
Proportional factor
Integrating factor
Derivative factor
Electric after-heating factors
Proportional factor
Integrating factor
Derivative factor
Heat pump factors - heating
Proportional factor
Integrating factor
Derivative factor
Heat pump factors - cooling
Proportional factor
Integrating factor
Derivative factor
Heat pump factors 2 - heating
Proportional factor
Integrating factor
Derivative factor
Heat pump factors 2 - cooling
Proportional factor
Integrating factor
Derivative factor
Heat pump factors 3 - heating
Proportional factor
Integrating factor
Derivative factor
Heat pump factors 3 - cooling
Proportional factor
Integrating factor
Derivative factor
Heat recovery RHE/BP PE
Proportional factor
Integrating factor
Derivative factor
Heat recovery AP factors
Proportional factor
Integrating factor
Derivative factor
Mixing factors
Proportional factor
Integrating factor
Derivative factor
Cooling factors
Proportional factor
Integrating factor
Derivative factor
Humidification factors
Proportional factor
Integrating factor
Derivative factor
Dehumidification factors
Proportional factor
Integrating factor
Derivative factor
Humidity cascade control factors
Proportional factor
Integrating factor
Heating-dependent fan speed compensation factors
Proportional factor
Integrating factor
Derivative factor
Cooling-dependent fan speed compensation factors
Proportional factor
Integrating factor
Derivative factor
Room (outlet) temperature-dependent fan speed compensation factors
Proportional factor
Integrating factor
Derivative factor
Humidity-dependent fan speed compensation factors
Factory settings
Value
Min
Max
Units
10
120
s
0
s
-10
120
s
0
s
5
120
s
0
s
1
60
s
0
s
5
300
s
0
s
-5
300
s
0
s
5
300
s
0
s
-5
300
s
0
s
5
300
s
0
s
-5
300
s
0
s
3
60
s
1
s
20
150
s
0
s
7
45
s
15
s
-5
60
s
0
s
5
120
s
0
s
-2
240
s
0
s
4
0
s
5
120
s
0
s
-10
120
s
0
s
20
0
s
0
s