Checking Data Link Status; Led Indicators; Data Link Status Area - Omron SYSMAC 3G8F7-CLK13-E Operation Manual

Controller link support boards for pci bus
Table of Contents

Advertisement

Checking Data Link Status

5-4

Checking Data Link Status

5-4-1

LED Indicators

Make sure that the LNK
indicator is ON at nodes
participating in the active
data links.
5-4-2

Data Link Status Area

There are two methods for checking the status of active data links:
• Check the LED indicators on the front of the Units.
• Check the data link status area.
Check the LNK indicator on the front of the Board.
Optical Ring Unit
(H-PCF or GI Cable)
Name
Color
LNK
Yellow
(data link)
The LNK indicator will be lit at all node participating in the data links as long
as operation is normal. The data link mode (manual/automatic) can be
checked using the M/A indicator. The M/A indicator is only available in the
Controller Link Unit and cannot be used in the Controller Link Support Board.
Refer to 9-1 Troubleshooting Using Indicators for details.
The data link status area can be used to check for errors when data link does
not operate normally even though no abnormality has been detected by the
computer or the Controller Link Support Board.
Data link status can be monitored using the CLK Data Link Setting Utility in
FinsGateway or it can be stored in FinsGateway event memory. Refer to the
FinsGateway online help and installation guide for details.
Wired Unit
Status
ON
Participating data links.
Flashing
Data link table setting error.
OFF
Not in data links or data links are inactive.
Section 5-4
Contents