Response Codes
Main code
21: Write not possible
22: Not executable in cur-
rent mode
23: No Unit
24: Start/stop not possi-
ble
114
Sub-
Probable cause
code
01
The specified area is read-only or is
write-protected.
02
The data is protected.
An attempt was made to simulta-
neously download and upload a file.
The data link tables cannot be written
manual because the Unit is set for
automatic generation.
03
The number of files exceeds the maxi-
mum permissible.
Too many files open.
05
A non-existing program no. has been
specified.
06
A non-existent file has been specified.
07
The specified file already exists.
08
Data cannot be changed.
01
The mode is wrong (executing).
Data links are active.
02
The mode is wrong (inactive).
Data links are active.
03
The PC is in the PROGRAM mode.
04
The PC is in the DEBUG mode.
05
The PC is in the MONITOR mode.
06
The PC is in the RUN mode.
07
The specified node is not the control
node.
08
The mode is wrong and the step can-
not be executed.
01
A file device does not exist where
specified.
02
The specified memory does not exist.
03
No clock exists.
01
The data link tables either have not
been created or are incorrect.
Remedy
If the specified area is read-only, the write
cannot be performed. If it is write-protected,
turn off the write-protect switch and execute
the instruction again.
Execute the instruction again after issuing
the PROGRAM AREA PROTECT CLEAR
command to the PC.
Check the file name and either interrupt ser-
vicing or wait for servicing to complete
before re-executing the command.
Change the data link mode to manual.
Write the file(s) again after erasing
unneeded files, or use different disk or
Memory Card that has free space.
Close open files and re-execute the com-
mand.
Check the program number and be sure
that it is set correctly.
---
Change the name of the file and execute
the instruction again.
Check the contents of the memory area
being written to.
Check the operating mode.
Check the data link status before execution.
Check the operating mode.
Check the data link status before execution.
Check the PC's mode and the computer
mode.
Check the PC's mode and the computer
mode.
Check the PC's mode and the computer
mode.
Check the PC's mode and the computer
mode.
Check which node is the control node.
Check whether the step has active status or
not.
Mount the Memory Card or disk
Check the specifications of the installed file
memory.
Check the model number.
Set the data link tables correctly.
Section 6-4