Omron SYSMAC 3G8F7-CLK13-E Operation Manual page 171

Controller link support boards for pci bus
Table of Contents

Advertisement

Error Log
Error
Contents
code
010D
Transmission failed; destination
Hex
address incorrect
010E
Transmission failed; routing
Hex
tables not registered
010F
Transmission failed; routing
Hex
table error
0110
Transmission failed; too many
Hex
relay points
0111
Transmission failed; command
Hex
packet too long
0112
Transmission failed; header
Hex
error.
0113
I/O setting error; cannot send.
Hex
0114
CPU bus error; cannot send.
Hex
0115
I/O duplication; cannot send.
Hex
0116
CPU Bus Unit error; cannot
Hex
send.
0117
Internal buffer full
Hex
0118
Illegal packet discarded
Hex
0124
Maximum frame length
Hex
exceeded; cannot route.
0203
EEPROM error
Hex
0206
Number of participating nodes
Hex
decreased (local node still partic-
ipating)
0207
Number of participating nodes
Hex
decreased (local node not partic-
ipating)
0208
polling node changed
Hex
0209
Network parameter disagree-
Hex
ment
020C
Time out with token
Hex
0210
Communications controller
Hex
transmitter error
Detail code
1st byte
2nd byte
Command block
Bits 0 to 7:
Source node address
Bits 8 to 14:
Source Network address
Bit 15:
OFF
Response block
Bits 0 to 7:
Destination node
address
Bits 8 to 14:
Destination Network
address
Bit 15:
ON
(1st byte: bits 8 to 15;
2nd byte, bits 0 to 7)
01 Hex:
01 Hex:
Read error
Data link
02: Hex:
tables
Write error
02 Hex: Net-
work param-
eters
03 Hex:
Routing
tables
Network
Number of
parameters
non-partici-
maximum
pating nodes
node
address
Address of
Address of
previous
new polling
polling node
node
00 Hex
Address of
polling node
00 Hex
Error status
(See note 4.)
00 Hex
Correction
Check routing tables.
Check routing tables and system
configuration. Do not try to access
Networks separated by more than
one other Network.
Be sure to use the correct FINS
command format.
Correct either the system configura-
tion or the registered I/O tables.
Check the Board and cable connec-
tions and clear the error.
Check the unit numbers to be sure
the same number is not set twice in
the same PC.
Check the Board and cable connec-
tions and clear the error.
Increase number of retries or recon-
figure system to distribute load.
Check for nodes sending illegal
data.
Correct the FINS command format.
Also, be sure that the parameters
specified for the command do not
produce a response that is too long.
Reset the relevant data. If the error
occurs again replace the Controller
Link Support Board.
Check network parameters, node
participation, cables, and terminating
resistance.
Check previous polling node.
Using the Controller Link Support
Software, check network parame-
ters.
Check network parameters, node
participation, cables, and terminating
resistance.
Replace the Controller Link Support
Board.
Section 9-3
Recorded
in
EEPROM
No
No
No
No
No
No
No
No
No
No
No
Yes
No
Yes
No (See
note 3.)
No (See
note 3.)
No (See
note 3.)
Yes
No
Yes
151