Error Codes - Omron SYSMAC 3G8F7-CLK13-E Operation Manual

Controller link support boards for pci bus
Table of Contents

Advertisement

Error Log
9-3-2

Error Codes

Error
Contents
code
0001
CPU Unit watchdog timer error
Hex
0002
CPU Unit service monitor error
Hex
0003
CPU Unit RAM error
Hex
0004
CPU Bus Unit ID number error
Hex
0005
Unit number error
Hex
0006
CPU error
Hex
000E
I/O bus error
Hex
000F
CPU Unit initialization error
Hex
0010
System capacity exceeded
Hex
0011
CPU Unit initialization timeout
Hex
0012
CPU Unit memory error
Hex
0013
CPU Unit write-protected
Hex
The following table lists the error codes (in 4-digit hexadecimal) and the con-
tents of the errors.
Detail code
1st byte
2nd byte
00 Hex
00 Hex
Monitor time (ms)
01 Hex:
00 Hex
Cyclic
02 Hex:
Event
04 Hex:
CPU bus link
00 Hex
00 Hex
Unit set
CPU Unit
value
detected
value
Bit 11: Unit missing in reg-
istered I/O tables
Bit 12: Hard test number
detected
Bit 13: Illegal number
detected
Bit 14: Unit number dupli-
cated
00 Hex
00 Hex
01 Hex:
01 Hex:
Read error
Data link
02 Hex:
tables
Write error
02 Hex: Net-
work param-
eters
03 Hex:
Routing
tables
04 Hex: Sys-
tem setup
Correction
Replace the CPU Unit.
Check the environment settings.
Check the environment settings.
Check the I/O tables.
Check the unit number settings and
recreate the I/O tables.
Check the unit number settings and
recreate the I/O tables.
Check the environment settings.
Check the environment settings.
Reduce the number of CPU Bus
Units mounted in one PC.
Check the environment settings.
Check the relevant settings.
Release write protection for the CPU
Unit.
Section 9-3
Recorded
in
EEPROM
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
149