2.6.3
Monitoring reference (Pr. 55
Set the frequency
or current which
is referenced
when the output
frequency or
output current is
selected for the
terminal FM.
Parameter
Frequency monitoring
55
reference
Current monitoring
56
reference
<Setting>
Refer to the above diagrams and set the frequency monitoring reference value in
Pr. 55 and the current monitoring reference value in Pr. 56.
Pr. 55 is set when Pr. 54 "FM terminal function selection" = "0" and Pr. 56 is set when
Pr. 54 = "1".
Set the Pr. 55 and Pr. 56 values so that the output pulse train output of terminal FM is
1440 pulses/s.
CAUTION
The maximum pulse train output of terminal FM is 2400 pulses/s. If Pr. 55 is not
adjusted, the output of terminal FM will be filled to capacity. Therefore, adjust
Pr. 55.

2.7 Restart operation function

2.7.1
Restart setting (Pr. 57
At power restoration after an instantaneous power failure, you can restart the
inverter without stopping the motor (with the motor coasting).
Parameter
57
Restart coasting time
58
Restart cushion time
Automatic restart after
H6 (162)
instantaneous power
failure selection
The parameter number in parentheses is the one for use with the parameter unit (FR-PU04).
1440 pulses/s (terminal FM)
Output
frequency
Name
Factory Setting
Rated inverter
Factory
Name
Setting
- - -
1s
1
, Pr. 56
Pr.55
Setting
Range
60Hz
0 to 120Hz
0 to 50A
current
, Pr. 58
Setting
Range
0 to 5s,
- - -
0 to 60s
Setting is enabled when Pr. 30 = "1"
0, 1, 10
101

Restart operation function

)
1440 pulses/s (terminal FM)
Output
Pr.56
frequency
Remarks
Setting is enabled when
Pr. 30 = "1"
, H6
)
Remarks
2