Changing example Deflecting the meter (analog indicator) to full-scale (1mA) at the
POINT
•The calibration parameters "C1" can be made to be ready by setting "1" (extended
function parameter valid) in Pr. 30 "extended function display selection".
•Set the value of the calibration parameter C1 "FM terminal calibration".
Operation
1.
Press the
MODE
parameter setting mode.
2.
Turn the
Pr. 30 must be set to "1".
(For details, refer to the instruction
manual (basic).)
3.
Press the
SET
"
" .
4.
Turn the
calibration parameter C1 "
terminal calibration" appears.
5.
Press the
SET
6.
If the inverter is at a stop, press the
to start it. (The motor
RUN
need not be connected.)
7.
Turn the
indicator needle to the
desired position.
8.
Press the
SET
Setting is complete.
preset frequency of 60Hz (for frequency setting, refer to the
instruction manual (basic).)
to choose the
"
" .
to show
to show
until the
FM
to enable setting.
to adjust the
.
By turning the
, you can read another parameter.
Press the
to return to the
SET
Press the
twice to show the next parameter (
SET
MODE
SET
SET
RUN
+
-
SET
Flicker ... Parameter setting complete!!
indication (step 3).
139
Calibration parameters
Display
The parameter
number read
previously
appears.
RUN
PU
EXT
Analog indicator
).
2