Operation selection function
REMARKS
•If the multi-speed (RH, RM, RL signal) or jog operation (JOG signal) is entered, PID control is
stopped and multi-speed or jog operation is started.
•Changing the terminal functions using Pr. 60 to Pr. 65 may affect the other functions. Confirm
the functions of the corresponding terminals before making settings.
•When PID control is selected, the minimum frequency is the frequency set in the calibration
parameter C2 and the maximum frequency is the frequency set in Pr. 38.
(The Pr. 1 "maximum frequency" and Pr. 2 "minimum frequency" settings are also valid.)
•When the control is switched to PID control during normal operation, the frequency command
value calculated by PID operation using 0Hz as standard is used without the frequency
during the operation.
PID action
Operation when control is switched to PID control during normal operation
Related parameters
X14 signal assignment ⇒ Pr. 60 to Pr. 63 (input terminal function selection) (refer to page 108)
FUP, FDN and RL signal assignment ⇒ Pr. 64 "RUN terminal function selection", Pr. 65 "A, B, C
terminal function selection" (refer to page 110)
Voltage input selection (0 to
(refer to page 114)
Operation mode selection ⇒ Pr. 79 "operation mode selection" (refer to page 119)
Making terminal calibration ⇒ Pr. 38, Pr. 39, C2 to C7 (calibration parameters) (refer to page 91)
Frequency
command
Normal operation
±
±
10V) ⇒ Pr. 73 "0-5V/0-10V selection"
5V, 0 to
PID set point
Frequency command
during normal operation
ON
PID operation
Normal operation
130