Mitsubishi Electric FR-S520E Series Instruction Manual page 207

Transistored inverter
Table of Contents

Advertisement

(2) Three-phase 400V power supply
Type FR-S540E- K
Applied motor capacity (kW) (*1)
Rated capacity (kVA) (*2)
Rated current (A)
Overload current rating (*3)
Voltage (*4)
Rated input AC voltage/frequency
Permissible AC voltage fluctuation
Permissible frequency fluctuation
Power supply system capacity
(kVA) (*5)
Protective structure (JEM1030)
Cooling system
Approximate mass (kg)
*1. The applied motor capacity indicated is the maximum capacity applicable for use of the
Mitsubishi 4-pole standard motor.
*2. The rated output capacity indicated assumes that the output voltage is 440V.
*3. The % value of the overload current rating indicated is the ratio of the overload current to
the inverter's rated output current.
For repeated duty, allow time for the inverter and motor to return to or below the
temperatures under 100% load.
*4. The maximum output voltage does not exceed the power supply voltage. You can set the
maximum output voltage to any value below the power supply voltage. However, the
pulse voltage value of the inverter output side voltage remains unchanged at about
that of the power supply.
*5. The power supply capacity varies with the value of the power supply side inverter
impedance (including those of the input reactor and cables).
0.4
0.75
0.4
0.75
0.9
1.6
1.1
2.1
150% 60s, 200% 0.5s (Inverse time characteristics)
Three phase, 380V to 480V
Three phase, 380V to 480V 50Hz/60Hz
325 to 528V 50Hz/60Hz
1.5
2.5
Enclosed type (IP20)
Self-cooling
1.5
1.5
197
Specification list
1.5
2.2
1.5
2.2
2.7
3.7
3.5
4.8
±5%
4.5
5.5
Forced air cooling
1.5
1.6
3.7
3.7
5.9
7.7
9.5
1.7
2
4