Monitoring Reference (Pr. 55 , Pr. 56 ); Restart Operation Parameters; Restart Setting (Pr. 57 , Pr. 58 , H6 ) - Mitsubishi Electric FR-S500E Instruction Manual

Frequency inverter
Table of Contents

Advertisement

Restart operation parameters

2.6.3
Monitoring reference (Pr. 55
Set the frequency
or current which
is referenced
when the output
frequency or
output current is
selected for the
terminal AM.
Parameter
Frequency monitoring
55
reference
Current monitoring
56
reference
<Setting>
Refer to the above diagrams and set the frequency monitoring reference value in
Pr. 55 and the current monitoring reference value in Pr. 56.
Pr. 55 is set when Pr. 54 "AM terminal function selection" = "0" and Pr. 56 is set when
Pr. 54 = "1".
In Pr. 55 and Pr. 56, set the frequency and current at which the output voltage of
terminal AM will be 5V.
CAUTION
The maximum output voltage of terminal AM is 5VDC.

2.7 Restart operation parameters

2.7.1
Restart setting (Pr. 57
At power restoration after an instantaneous power failure, you can restart the
inverter without stopping the motor (with the motor coasting).
Parameter
57
Restart coasting time
58
Restart cushion time
Automatic restart after
H6 (162)
instantaneous power
failure selection
The parameter number in parentheses is the one for use with the parameter unit (FR-PU04).
5VDC (terminal AM)
Output
frequency
Name
Factory Setting
Rated output
Factory
Name
Setting
- - -
1s
1
, Pr. 56
Pr.55
Setting
Range
50Hz
0 to 120Hz
0 to 50A
current
, Pr. 58
Setting
Range
0 to 5s,
- - -
0 to 60s
Setting is enabled when Pr. 30 = "1"
0, 1, 10
90
)
5VDC (terminal AM)
Output
Pr.56
frequency
Remarks
Setting is enabled when
Pr. 30 = "1"
, H6
)
Remarks