5.2.2

LCL filter

Enough free space must be left around the LCL filter to ensure sufficient air circulation and cooling.
You will find the required dimensions for free space in the Table 23. You will find the required
cooling air, minimum air holes and heat dissipation in the Table 24.
When planning the cooling for the space, take into consideration that the LCL filter heat loss is
approx. 1% of the nominal capacity. Air flow, see Figure 37 and Figure 38.
A = free space above the LCL filter
B
B
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
Table 23.
Mounting space dimensions
Type
A
LCL0261 5
350
LCL0170 6
LCL0460 5
350
LCL0325 6
LCL1300 5
350
LCL1030 6
= distance between LCL filter and cabinet wall
B2
Figure 36. Installation space
Dimensions [mm]