Alternating Voltage
Voltage supply using integrated converter
Nominal auxiliary AC voltage U
admissible voltage ranges
Power input
- quiescent
- energized
plus approx. 1.5 VA per interface module
Bridging time for failure/short circuit of alternating
auxiliary voltage
4.1.3

Binary Inputs and Outputs

Binary Inputs
Variant
7VK610
7VK611
Rated voltage range
Switching Thresholds
- for rated voltages
- for rated voltages
- for rated voltages
Current consumption, energized
Maximum admissible voltage
Input Impulse suppression
Binary Outputs
Signalling/command relays (see also overview diagrams in Appendix A)
Quantity and information
Order variant
7VK610
7VK611
Switching Capability BRAKE
Switching capability OFF
Switching voltage
DC
SIPROTEC, 7VK61, Manual
C53000-G1176-C159-3, Release date 05.2009
115 VAC
Aux
92 to 132 V~
7VK610
7VK611
≥ 50 ms
Quantity
7 (configurable)
20 (configurable)
24 VDC to 250 VDC, in 3 ranges, bipolar
Switching Thresholds, adjustable voltage range with jumpers
24/48 VDC
60/110/125 VDC
110/125/220/250 VDC
220/250 VDC
approx. 1.8 mA
independent of the control voltage
300 VDC
220 nF coupling capacitance at 220 V with recovery time >
60 ms
depending on ordered version:
NO-contact (normal-
ly open contact)
250 V
NO/NC (switch selectable)
5
17
1000 W/VA
30 VA
40 W resistive 25 W/VA at L/R ≤ 50 ms
Technical Data
4.1 General
230 VAC
184 to 265 V~
approx. 7 VA
approx.12 VA
approx. 17 VA
Uto ≥ 19 VDC
Ufrom ≤ 14 VDC
Uto ≥ 88 VDC
Ufrom ≤ 66 VDC
Uto ≥ 176 VDC
Ufrom ≤ 117 VDC