Siemens Siprotec 7VK61 Manual page 291

Breaker management device
Hide thumbs Also See for Siprotec 7VK61:
Table of Contents

Advertisement

Addr.
Parameter
3519
AR OVERRIDE
3530
Op.mode with MC
3531
MC maxVolt.Diff
3532
MC maxFreq.Diff
3533
MC maxAngleDiff
3535A
MC SYNCHR
3536
MC Usy1< Usy2>
3537
MC Usy1> Usy2<
3538
MC Usy1< Usy2<
3539
MC OVERRIDE
3701
Uph-e>(>)
3702
Uph-e>
3703
T Uph-e>
3704
Uph-e>>
3705
T Uph-e>>
3709A
Uph-e>(>) RESET
3711
Uph-ph>(>)
3712
Uph-ph>
3713
T Uph-ph>
3714
Uph-ph>>
3715
T Uph-ph>>
3719A
Uphph>(>) RESET
3721
3U0>(>) (or Ux)
3722
3U0>
3723
T 3U0>
3724
3U0>>
3725
T 3U0>>
3728A
3U0>(>) Stabil.
3729A
3U0>(>) RESET
3731
U1>(>)
3732
U1>
3733
T U1>
3734
U1>>
3735
T U1>>
3739A
U1>(>) RESET
3741
U2>(>)
3742
U2>
3743
T U2>
3744
U2>>
SIPROTEC, 7VK61, Manual
C53000-G1176-C159-3, Release date 05.2009
Function
C
Sync. Check
YES
NO
Sync. Check
with T-CB close
w/o T-CB close
Sync. Check
1.0 .. 60.0 V
Sync. Check
0.03 .. 2.00 Hz
Sync. Check
2 .. 80 °
Sync. Check
YES
NO
Sync. Check
YES
NO
Sync. Check
YES
NO
Sync. Check
YES
NO
Sync. Check
YES
NO
Voltage Prot.
OFF
Alarm Only
ON
U>Alarm U>>Trip
1.0 .. 170.0 V; ∞
Voltage Prot.
0.00 .. 100.00 sec; ∞
Voltage Prot.
1.0 .. 170.0 V; ∞
Voltage Prot.
0.00 .. 100.00 sec; ∞
Voltage Prot.
Voltage Prot.
0.30 .. 0.99
Voltage Prot.
OFF
Alarm Only
ON
U>Alarm U>>Trip
2.0 .. 220.0 V; ∞
Voltage Prot.
0.00 .. 100.00 sec; ∞
Voltage Prot.
2.0 .. 220.0 V; ∞
Voltage Prot.
0.00 .. 100.00 sec; ∞
Voltage Prot.
Voltage Prot.
0.30 .. 0.99
Voltage Prot.
OFF
Alarm Only
ON
U>Alarm U>>Trip
1.0 .. 220.0 V; ∞
Voltage Prot.
0.00 .. 100.00 sec; ∞
Voltage Prot.
1.0 .. 220.0 V; ∞
Voltage Prot.
0.00 .. 100.00 sec; ∞
Voltage Prot.
Voltage Prot.
ON
OFF
Voltage Prot.
0.30 .. 0.99
Voltage Prot.
OFF
Alarm Only
ON
U>Alarm U>>Trip
2.0 .. 220.0 V; ∞
Voltage Prot.
0.00 .. 100.00 sec; ∞
Voltage Prot.
2.0 .. 220.0 V; ∞
Voltage Prot.
0.00 .. 100.00 sec; ∞
Voltage Prot.
Voltage Prot.
0.30 .. 0.99
Voltage Prot.
OFF
Alarm Only
ON
U>Alarm U>>Trip
2.0 .. 220.0 V; ∞
Voltage Prot.
0.00 .. 100.00 sec; ∞
Voltage Prot.
2.0 .. 220.0 V; ∞
Voltage Prot.
Setting Options
Default Setting
NO
w/o T-CB close
2.0 V
0.10 Hz
10 °
YES
NO
NO
NO
NO
OFF
85.0 V
2.00 sec
100.0 V
1.00 sec
0.98
OFF
150.0 V
2.00 sec
175.0 V
1.00 sec
0.98
OFF
30.0 V
2.00 sec
50.0 V
1.00 sec
ON
0.95
OFF
150.0 V
2.00 sec
175.0 V
1.00 sec
0.98
OFF
30.0 V
2.00 sec
50.0 V
Appendix
A.7 Settings
Comments
Override of any check before AR
Operating mode with Man.Cl
Maximum voltage difference
Maximum frequency difference
Maximum angle difference
Manual Close at Usy2>, Usy1>,
and Synchr
Manual Close at Usy1< and
Usy2>
Manual Close at Usy1> and
Usy2<
Manual Close at Usy1< and
Usy2<
Override of any check before
Man.Cl
Operating mode Uph-e overvolt-
age prot.
Uph-e> Pickup
T Uph-e> Time Delay
Uph-e>> Pickup
T Uph-e>> Time Delay
Uph-e>(>) Reset ratio
Operating mode Uph-ph over-
voltage prot.
Uph-ph> Pickup
T Uph-ph> Time Delay
Uph-ph>> Pickup
T Uph-ph>> Time Delay
Uph-ph>(>) Reset ratio
Operating mode 3U0 (or Ux) ov-
ervoltage
3U0> Pickup (or Ux>)
T 3U0> Time Delay (or T Ux>)
3U0>> Pickup (or Ux>>)
T 3U0>> Time Delay (or T Ux>>)
3U0>(>): Stabilization 3U0-Mea-
surement
3U0>(>) Reset ratio (or Ux)
Operating mode U1 overvoltage
prot.
U1> Pickup
T U1> Time Delay
U1>> Pickup
T U1>> Time Delay
U1>(>) Reset ratio
Operating mode U2 overvoltage
prot.
U2> Pickup
T U2> Time Delay
U2>> Pickup
291