Functions
2.1 General
breaker auxiliary contact must send a message that the circuit breaker is open. It is a prerequisite for this setting
that the position of the auxiliary contact is allocated via a binary input.

2.1.5.2 Settings

Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings.
The table indicates region-specific presettings. Column C (configuration) indicates the corresponding second-
ary nominal current of the current transformer.
Addr.
Parameter
1103
FullScaleVolt.
1104
FullScaleCurr.
1107
P,Q sign
1130A
PoleOpenCurrent
1131A
PoleOpenVoltage
1133A
T DELAY SOTF
1135
Reset Trip CMD
1136
OpenPoleDetect.
1150A
SI Time Man.Cl
1151
MAN. CLOSE
1152
Man.Clos. Imp.

2.1.5.3 Information List

No.
Information
301
Pow.Sys.Flt.
302
Fault Event
351
>CB Aux. L1
352
>CB Aux. L2
353
>CB Aux. L3
356
>Manual Close
357
>Blk Man. Close
38
C
Setting Options
1.0 .. 1200.0 kV
10 .. 5000 A
not reversed
reversed
1A
0.05 .. 1.00 A
5A
0.25 .. 5.00 A
2 .. 70 V
0.05 .. 30.00 sec
CurrentOpenPole
Current AND CB
Pickup Reset
OFF
Current AND CB
w/ measurement
0.01 .. 30.00 sec
with Sync-check
w/o Sync-check
NO
(Setting options depend
on configuration)
Type of In-
formation
OUT
Power System fault
OUT
Fault Event
SP
>Circuit breaker aux. contact: Pole L1
SP
>Circuit breaker aux. contact: Pole L2
SP
>Circuit breaker aux. contact: Pole L3
SP
>Manual close signal
SP
>Block manual close cmd. from external
Default Setting
400.0 kV
Measurement: Full Scale
Voltage (100%)
1000 A
Measurement: Full Scale
Current (100%)
not reversed
P,Q operational measured
values sign
0.10 A
Pole Open Current
Threshold
0.50 A
30 V
Pole Open Voltage
Threshold
0.25 sec
minimal time for line open
before SOTF
CurrentOpenPole
RESET of Trip Command
w/ measurement
open pole detector
0.30 sec
Seal-in Time after
MANUAL closures
NO
Manual CLOSE
COMMAND generation
None
MANUAL Closure Impulse
after CONTROL
Comments
SIPROTEC, 7VK61, Manual
C53000-G1176-C159-3, Release date 05.2009