Addr.
Parameter
3759A
Uph-e<(<) RESET
3761
Uph-ph<(<)
3762
Uph-ph<
3763
T Uph-ph<
3764
Uph-ph<<
3765
T Uphph<<
3768
CURR.SUP.Uphph<
3769A
Uphph<(<) RESET
3771
U1<(<)
3772
U1<
3773
T U1<
3774
U1<<
3775
T U1<<
3778
CURR.SUP.U1<
3779A
U1<(<) RESET
2.5.5

Information List

No.
Information
234.2100 U<, U> blk
10201
>Uph-e>(>) BLK
10202
>Uph-ph>(>) BLK
10203
>3U0>(>) BLK
10204
>U1>(>) BLK
10205
>U2>(>) BLK
10206
>Uph-e<(<) BLK
10207
>Uphph<(<) BLK
10208
>U1<(<) BLK
10215
Uph-e>(>) OFF
10216
Uph-e>(>) BLK
10217
Uph-ph>(>) OFF
10218
Uph-ph>(>) BLK
10219
3U0>(>) OFF
10220
3U0>(>) BLK
10221
U1>(>) OFF
SIPROTEC, 7VK61, Manual
C53000-G1176-C159-3, Release date 05.2009
Setting Options
1.01 .. 1.20
OFF
Alarm Only
ON
U<Alarm U<<Trip
1.0 .. 175.0 V; 0
0.00 .. 100.00 sec; ∞
1.0 .. 175.0 V; 0
0.00 .. 100.00 sec; ∞
ON
OFF
1.01 .. 1.20
OFF
Alarm Only
ON
U<Alarm U<<Trip
1.0 .. 100.0 V; 0
0.00 .. 100.00 sec; ∞
1.0 .. 100.0 V; 0
0.00 .. 100.00 sec; ∞
ON
OFF
1.01 .. 1.20
Type of In-
formation
IntSP
U<, U> blocked via operation
SP
>BLOCK Uph-e>(>) Overvolt. (phase-earth)
SP
>BLOCK Uph-ph>(>) Overvolt (phase-phase)
SP
>BLOCK 3U0>(>) Overvolt. (zero sequence)
SP
>BLOCK U1>(>) Overvolt. (positive seq.)
SP
>BLOCK U2>(>) Overvolt. (negative seq.)
SP
>BLOCK Uph-e<(<) Undervolt (phase-earth)
SP
>BLOCK Uphph<(<) Undervolt (phase-phase)
SP
>BLOCK U1<(<) Undervolt (positive seq.)
OUT
Uph-e>(>) Overvolt. is switched OFF
OUT
Uph-e>(>) Overvolt. is BLOCKED
OUT
Uph-ph>(>) Overvolt. is switched OFF
OUT
Uph-ph>(>) Overvolt. is BLOCKED
OUT
3U0>(>) Overvolt. is switched OFF
OUT
3U0>(>) Overvolt. is BLOCKED
OUT
U1>(>) Overvolt. is switched OFF
2.5 Under and over-voltage protection (optional)
Default Setting
1.05
Uph-e<(<) Reset ratio
OFF
Operating mode Uph-ph under-
voltage prot.
50.0 V
Uph-ph< Pickup
2.00 sec
T Uph-ph< Time Delay
17.0 V
Uph-ph<< Pickup
1.00 sec
T Uph-ph<< Time Delay
ON
Current supervision (Uph-ph)
1.05
Uph-ph<(<) Reset ratio
OFF
Operating mode U1 undervoltage
prot.
30.0 V
U1< Pickup
2.00 sec
T U1< Time Delay
10.0 V
U1<< Pickup
1.00 sec
T U1<< Time Delay
ON
Current supervision (U1)
1.05
U1<(<) Reset ratio
Comments
Functions
Comments
111