4.4 Synchronism and Voltage Check (optional)

4.4
Synchronism and Voltage Check (optional)
Operating modes
Operating modes
with automatic reclosure
Synchronism
Operating modes
for manual closure
Voltages
Maximum operating voltage
U< for dead status
U> for live status
Tolerances
Dropout to pickup ratio
ΔU Measurement
Voltage difference
Tolerance
Dropout to pickup ratio
Synchronous power conditions
Δϕ-measurement
Tolerance
Δf-measurement
Tolerance
Enable delay
Asynchronous power conditions
Δf-measurement
Tolerance
Max. angle error
Synchronous/asynchronous limits
Circuit breaker operating time
248
Synchronism check
Live bus - dead line
Dead bus - live line
Dead bus and dead line
Bypassing
Or combination of the above
Closing the circuit breaker under asynchronous power condi-
tions possible (with circuit breaker action time)
As for automatic reclosure,
independently selectable
20 V to 140 V (phase-to-phase)
1 V to 60 V (phase-to-phase)
20 V to 125 V (phase-to-phase)
2 % of pickup value or 1 V
Approx. 0.9 (U>) or 1.1 (U<)
1.0 V to 60.0 V (phase-to-phase)
1 V
Approx. 1.05
2° to 80°
0.03 Hz to 2.00 Hz
15 mHz
0.00 s to 30.00 s
0.03 Hz to 2.00 Hz
15 mHz
5° for Δf ≤ 1 Hz
10° for Δf > 1 Hz
0.01 Hz
0.01 s to 0.60 s
C53000-G1176-C159-3, Release date 05.2009
Increments 1 V
Increments 1 V
Increments 1 V
Increments 0.1V
Increments 1°
Increments 0.01 Hz
Increments 0.01 s
Increments 0.01 Hz
Increments 0.01 s
SIPROTEC, 7VK61, Manual