To achieve three pole coupling of the external protection and to release, if necessary, its accelerated stages
before reclosure, the following output functions are suitable:
2864 „AR 1p Trip Perm"
2889 „AR 1.CycZoneRel"
2820 „AR Program1pole"
Instead of the three phase-segregated trip commands, the single-pole and three-pole tripping may also be sig-
nalled to the internal automatic reclosure function - provided that the external protection device is capable of
this -, i.e. assign the following binary inputs of the 7VK61:
2711 „>AR Start"
2715 „>Trip 1pole AR"
2716 „>Trip 3pole AR"
If only three-pole reclosure cycles are to be executed, it is sufficient to assign the binary input „>Trip 3pole
AR" (no. 2716) for the trip signal. Figure 2-8 shows an example. Any overreaching stages of the external pro-
tection are enabled again by „AR 1.CycZoneRel" (no. 2889) and, if necessary, of further cycles.
Figure 2-8
SIPROTEC, 7VK61, Manual
C53000-G1176-C159-3, Release date 05.2009
Internal automatic reclosure function ready for single-pole reclose cycle, i.e.
allows single-pole tripping (logic inversion of the three-pole coupling).
Internal automatic reclosure function ready for the first reclose cycle, i.e. re-
leases the stage of the external protection device for reclosure, the corre-
sponding outputs can be used for other cycles. This output can be omitted if
the external protection does not require an overreaching stage (e.g. differ-
ential protection or comparison mode with distance protection).
Internal automatic reclosure function is programmed for one pole, i.e. only
recloses after single-pole tripping. This output can be omitted if no over-
reaching stage is required (e.g. differential protection or comparison mode
with distance protection).
General fault detection for the internal automatic reclosure function (only re-
quired for action time),
Trip command single-pole for the internal automatic reclosure,
Trip command three-pole for the internal automatic reclosure function,
Connection example with external protection device for 1-/3-pole reclosure; AR control mode
= with TRIP
2.2 Automatic reclosure function (optional)
Functions
53