For the 3rd cycle:
3472 3.AR: START
3473 3.AR: T-ACTION
3475 3.AR Tdead 1Flt
3476 3.AR Tdead 2Flt
3477 3.AR Tdead 3Flt
3478 3.AR Tdead1Trip
3479 3.AR Tdead3Trip
3480 3.AR: Tdead EV.
3481 3.AR: CB? CLOSE
3482 3.AR SynRequest
For the 4th cycle:
3483 4.AR: START
3484 4.AR: T-ACTION
3486 4.AR Tdead 1Flt
3487 4.AR Tdead 2Flt
3488 4.AR Tdead 3Flt
3489 4.AR Tdead1Trip
3490 4.AR Tdead3Trip
3491 4.AR: Tdead EV.
3492 4.AR: CB? CLOSE
3493 4.AR SynRequest
5th to 8th reclosure cycle
If more than four cycles were set during configuration of the functional scope, the dead times preceding the fifth
(5th) through the ninth (9th) reclosing attempts are equal to the open breaker time which precedes the fourth
(4th) reclosing attempt.
Notes on the Information Overview
The most important information about automatic reclosure is briefly explained insofar as it was not mentioned
in the following lists or described in detail in the preceding text.
„>BLK 1.AR-cycle" (No. 2742) to „>BLK 4.-n. AR" (No. 2745)
The respective auto-reclose cycle is blocked. If the blocking state already exists when the automatic reclosure
function is initiated, the blocked cycle is not executed and may be skipped (if other cycles are permitted). The
same applies if the automatic reclosure function is started (running), but not internally blocked. If the block
signal of a cycle appears while this cycle is being executed (in progress), the automatic reclosure function is
blocked dynamically; no further automatic reclosures cycles are then executed.
„AR 1.CycZoneRel" (No. 2889) to „AR 4.CycZoneRel" (No. 2892)
The automatic reclosure is ready for the respective reclosure cycle. This information indicates which cycle will
be run next. For example, external protection functions can use this information to release accelerated or over-
reaching trip stages prior to the corresponding reclose cycle.
SIPROTEC, 7VK61, Manual
C53000-G1176-C159-3, Release date 05.2009
Start in 3rd cycle generally allowed
Action time for the 3rd cycle
Dead time after single-phase pickup
Dead time after two-phase pickup
Dead time after three-phase pickup
Dead time after single-pole tripping
Dead time after three-pole tripping
Dead time after evolving fault
CB ready interrogation before reclosing
Sync. check after three-pole tripping
Start in 4th cycle generally allowed
Action time for the 4th cycle
Dead time after single-phase pickup
Dead time after two-phase pickup
Dead time after three-phase pickup
Dead time after single-pole tripping
Dead time after three-pole tripping
Dead time after evolving fault
CB ready interrogation before reclosing
Sync. check after three-pole tripping
2.2 Automatic reclosure function (optional)