Siemens Siprotec 7VK61 Manual page 151

Breaker management device
Hide thumbs Also See for Siprotec 7VK61:
Table of Contents

Advertisement

Reclosure via the integrated control functions - on-site control, control via DIGSI, control via serial interface -
can have the same effect as manual closure, see parameter 1152 Chapter 2.1.5.1 at margin heading „Circuit
Breaker Status".
If the device has an integrated automatic reclosure, the integrated manual closure logic of the 7VK61 automat-
ically distinguishes between an external control command via the binary input and an automatic reclosure by
the internal automatic reclosure so that the binary input „>Manual Close" can be connected directly to the
control circuit of the close coil of the circuit breaker (Figure 2-58). Each closing operation that is not initiated by
the internal automatic reclosure function is interpreted as a manual closure, even it has been initiated by a
control command from the device.
Figure 2-58
CB
ON
CBaux
If, however, external close commands which should not activate the manual close function are possible (e.g.
external reclosure device), the binary input „>Manual Close" must be triggered by a separate contact at the
control discrepancy switch (Figure 2-59).
If in the latter case a manual close command can also be given by means of an internal control command from
the device, such a command must be combined with the manual CLOSE function via parameter 1152
Man.Clos. Imp. (Figure 2-57).
SIPROTEC, 7VK61, Manual
C53000-G1176-C159-3, Release date 05.2009
Manual closure with internal automatic reclosure
Circuit breaker
Circuit breaker close coil
Circuit breaker auxiliary contact
Functions
2.8 Function Control
151