Settings - Siemens Siprotec 7VK61 Manual

Breaker management device
Hide thumbs Also See for Siprotec 7VK61:
Table of Contents

Advertisement

Functions
2.1 General

2.1.3.2 Settings

Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings.
Addr.
Parameter
201
CT Starpoint
203
Unom PRIMARY
204
Unom SECONDARY
205
CT PRIMARY
206
CT SECONDARY
207
SystemStarpoint
210
U4 transformer
211
Uph / Udelta
212
Usy2 connection
ϕ Usy2-Usy1
214A
215
Usy1/Usy2 ratio
220
I4 transformer
221
I4/Iph CT
230
Rated Frequency
235
PHASE SEQ.
239
T-CB close
240A
TMin TRIP CMD
241A
TMax CLOSE CMD
242
T-CBtest-dead
34
Setting Options
towards Line
towards Busbar
1.0 .. 1200.0 kV
80 .. 125 V
10 .. 5000 A
1A
5A
Solid Earthed
Peterson-Coil
Isolated
Not connected
Udelta transf.
Usy2 transf.
Ux transformer
0.10 .. 9.99
L1-E
L2-E
L3-E
L1-L2
L2-L3
L3-L1
0 .. 360 °
0.50 .. 2.00
Not connected
In prot. line
0.010 .. 5.000
50 Hz
60 Hz
L1 L2 L3
L1 L3 L2
0.01 .. 0.60 sec
0.02 .. 30.00 sec
0.01 .. 30.00 sec
0.00 .. 30.00 sec
Default Setting
towards Line
CT Starpoint
400.0 kV
Rated Primary Voltage
100 V
Rated Secondary Voltage (Ph-Ph)
1000 A
CT Rated Primary Current
1A
CT Rated Secondary Current
Solid Earthed
System Starpoint is
Not connected
U4 voltage transformer is
1.73
Matching ratio Phase-VT To
Open-Delta-VT
L1-L2
VT connection for Usy2
0 °
Angle adjustment Usy2-Usy1
1.00
Matching ratio Usy1 / Usy2
In prot. line
I4 current transformer is
1.000
Matching ratio I4/Iph for CT's
50 Hz
Rated Frequency
L1 L2 L3
Phase Sequence
0.06 sec
Closing (operating) time of CB
0.10 sec
Minimum TRIP Command Dura-
tion
0.10 sec
Maximum Close Command Dura-
tion
0.10 sec
Dead Time for CB test-autoreclo-
sure
C53000-G1176-C159-3, Release date 05.2009