Siemens Siprotec 7VK61 Manual page 209

Breaker management device
Hide thumbs Also See for Siprotec 7VK61:
Table of Contents

Advertisement

Time Synchronisation Interface
It is optionally possible to process 5 V, 12 V or 24 V time synchronization signals, provided that these are con-
nected to the inputs named in the following table.
Table 3-21
Pin No.
1
2
3
4
5
6
7
8
9
1)
Assigned, but cannot be used
Fibre-optic Cables
WARNING!
Laser rays!
Do not look directly into the fiber-optic elements!
Signals transmitted via optical fibers are unaffected by interference. The fibers guarantee electrical isolation
between the connections. Transmit and receive connections are represented by symbols.
The character idle state for the optical fibre interface is „Light off". If the character idle state is to be changed,
use the operating program DIGSI, as described in the SIPROTEC 4 System Description.
Further Connections
For further connections a visual inspection is sufficient for the time being. Electrical and functional controls are
performed during commissioning (see the following main section).
SIPROTEC, 7VK61, Manual
C53000-G1176-C159-3, Release date 05.2009
D-subminiature connector assignment of the time synchronization interface
Designation
P24_TSIG
P5_TSIG
M_TSIG
1)
-
SHIELD
-
P12_TSIG
P_TSYNC
SHIELD
1)
Mounting and Commissioning
3.2 Checking Connections
Signal meaning
Input 24 V
Input 5 V
Return line
1)
-
Shield potential
-
Input 12 V
1)
Input 24 V
Shield potential
209