Mounting and Commissioning
3.1 Mounting and Connections
Table 3-12
Jumper
X51
X60
X61
X62
X63
X64
1)
Not for variant with sensitive earth fault detection
Contacts of relays for binary outputs BO6, BO7 and BO8 can be configured as normally open or normally
closed (see also General Diagrams in the Appendix).
Table 3-13
For
BO6
BO7
BO8
1)
Factory setting
The relays for binary outputs BO1 through BO5 can be connected to common potential, or configured individ-
ually for BO1, BO4 and BO5 (BO2 and BO3 are without function in this context) (see also General Diagrams
in the Appendix).
Table 3-14
Jumper
X80
X81
X82
1)
Factory setting
The jumpers X71, X72 through X73 serve for setting the bus address. Their position may not be changed. The
following table shows the preset jumper positions.
Table 3-15
196
Jumper setting for nominal current or measuring range
Nominal current 1 A
Measuring range 20 A
1)
Jumper setting for the contact type of the relays for BO6, BO7 and BO8
Jumper
Open in quiescent state (NO)
X41
X42
X43
Jumper settings for the configuration of the common potential of BO1 through BO5 or for con-
figuration of BO1, BO4 and BO5 as single relays
BO1 through BO5 connected
to common potential
1-2, 3-4
1-2, 3-4
2-3
Jumper settings of module addresses of the input/output module C-I/O-2
Jumper
X71
X72
X73
1-2
1-2
2-5
2-5
2-5
2-5
1)
1-2
1-2
1-2
BO1, BO4, BO5 configured as single relays
1)
(BO2, BO3 without function)
Factory setting
C53000-G1176-C159-3, Release date 05.2009
Nominal current 5 A
Measuring range 100 A
1-2
2-3
3-5
3-5
3-5
3-5
Closed in quiescent state (NC)
2-3
2-3
2-3
2-3, 4-5
2-3, 4-5
1-2
1-2 (H)
1-2 (H)
2-3 (L)
SIPROTEC, 7VK61, Manual