4.4 Binary Output Allocation for Circuit Breaker Tripping
The following User Output to Binary Output allocations complete our ARC Fault Trip with Current Check.
SARC Operation
Zone Coverage
SARC 1
Feeder Exit Termination
Chamber
SARC 2
Feeder CB Chamber
Bus
SARC 3 or SARC 4
SARC 5
Incomer CB Chamber
SARC 6
Incomer Termination
Chamber
The screenshot shows the User Output to Binary Output allocation in the setting editor of Reydisp Manager.
Complete any other Protection settings otherwise required and save your setting.
4.5 Device Sync
With all IED settings, IED Logic and IEC61850 configuration complete we now need to
Synchronize the device.
Reydisp Manager will manage the file transfer process to the 7SR22 IED and upon completion the
7SR22 will be able subscribe to SARC Goose messages from the RA24 IED.
©2014 Siemens Protection Devices Limited
User Output Binary Output Trip
User Output 1 BO2
User Output 2 BO3
User Output 2 BO3
User Output 3 BO4
User Output 3 BO4
Table 6: Binary Output Allocation
Figure 46: Reydisp Relay Settings
Chapter 2) 7XG3124 Application Guide
1A CB
TR1 LT CB
TR1 LT CB
Upstream
Upstream
Chapter 2 Page 37 of 42