Siemens Siprotec 7VK61 Manual page 64

Breaker management device
Hide thumbs Also See for Siprotec 7VK61:
Table of Contents

Advertisement

Functions
2.2 Automatic reclosure function (optional)
Addr.
Parameter
3462
2.AR: T-ACTION
3464
2.AR Tdead 1Flt
3465
2.AR Tdead 2Flt
3466
2.AR Tdead 3Flt
3467
2.AR Tdead1Trip
3468
2.AR Tdead3Trip
3469
2.AR: Tdead EV.
3470
2.AR: CB? CLOSE
3471
2.AR SynRequest
3472
3.AR: START
3473
3.AR: T-ACTION
3475
3.AR Tdead 1Flt
3476
3.AR Tdead 2Flt
3477
3.AR Tdead 3Flt
3478
3.AR Tdead1Trip
3479
3.AR Tdead3Trip
3480
3.AR: Tdead EV.
3481
3.AR: CB? CLOSE
3482
3.AR SynRequest
3483
4.AR: START
3484
4.AR: T-ACTION
3486
4.AR Tdead 1Flt
3487
4.AR Tdead 2Flt
3488
4.AR Tdead 3Flt
3489
4.AR Tdead1Trip
3490
4.AR Tdead3Trip
3491
4.AR: Tdead EV.
3492
4.AR: CB? CLOSE
3493
4.AR SynRequest
64
Setting Options
0.01 .. 300.00 sec; ∞
0.01 .. 1800.00 sec; ∞
0.01 .. 1800.00 sec; ∞
0.01 .. 1800.00 sec; ∞
0.01 .. 1800.00 sec; ∞
0.01 .. 1800.00 sec; ∞
0.01 .. 1800.00 sec
YES
NO
YES
NO
YES
NO
0.01 .. 300.00 sec; ∞
0.01 .. 1800.00 sec; ∞
0.01 .. 1800.00 sec; ∞
0.01 .. 1800.00 sec; ∞
0.01 .. 1800.00 sec; ∞
0.01 .. 1800.00 sec; ∞
0.01 .. 1800.00 sec
YES
NO
YES
NO
YES
NO
0.01 .. 300.00 sec; ∞
0.01 .. 1800.00 sec; ∞
0.01 .. 1800.00 sec; ∞
0.01 .. 1800.00 sec; ∞
0.01 .. 1800.00 sec; ∞
0.01 .. 1800.00 sec; ∞
0.01 .. 1800.00 sec
YES
NO
YES
NO
Default Setting
0.20 sec
Action time
1.20 sec
Dead time after 1phase faults
1.20 sec
Dead time after 2phase faults
0.50 sec
Dead time after 3phase faults
∞ sec
Dead time after 1pole trip
0.50 sec
Dead time after 3pole trip
1.20 sec
Dead time after evolving fault
NO
CB ready interrogation before re-
closing
NO
Request for synchro-check after
3pole AR
NO
AR start allowed in this cycle
0.20 sec
Action time
1.20 sec
Dead time after 1phase faults
1.20 sec
Dead time after 2phase faults
0.50 sec
Dead time after 3phase faults
∞ sec
Dead time after 1pole trip
0.50 sec
Dead time after 3pole trip
1.20 sec
Dead time after evolving fault
NO
CB ready interrogation before re-
closing
NO
Request for synchro-check after
3pole AR
NO
AR start allowed in this cycle
0.20 sec
Action time
1.20 sec
Dead time after 1phase faults
1.20 sec
Dead time after 2phase faults
0.50 sec
Dead time after 3phase faults
∞ sec
Dead time after 1pole trip
0.50 sec
Dead time after 3pole trip
1.20 sec
Dead time after evolving fault
NO
CB ready interrogation before re-
closing
NO
Request for synchro-check after
3pole AR
C53000-G1176-C159-3, Release date 05.2009