Addr.
Parameter
3931
PoleDiscrepancy
3932
T-PoleDiscrep.
4001
FCT TripSuperv.
4002
No. of BI
4003
Alarm Delay
SIPROTEC, 7VK61, Manual
C53000-G1176-C159-3, Release date 05.2009
Function
C
Breaker Failure
ON
OFF
0.00 .. 30.00 sec; ∞
Breaker Failure
TripCirc.Superv
ON
OFF
TripCirc.Superv
1 .. 2
TripCirc.Superv
1 .. 30 sec
Setting Options
Default Setting
OFF
2.00 sec
OFF
2
2 sec
Appendix
A.7 Settings
Comments
Pole Discrepancy supervision
Trip delay with pole discrepancy
TRIP Circuit Supervision is
Number of Binary Inputs per trip
circuit
Delay Time for alarm
293