Introduction; Warning & Safety Information; Qualified Person; Danger - Siemens TPS3 01 Internal Manual

Surge protective device tps3 series
Table of Contents

Advertisement

Introduction

Thank you for choosing Siemens TPS3 Surge Protective Device (SPD).
This is a high quality, high energy surge suppressor designed to protect
sensitive equipment from damaging transient overvoltages.
Proper installation is important to maximize performance. Please follow
the steps outlined herein.
This entire user manual should be read prior to beginning installation.
These instructions are not intended to replace national or local codes.
Follow all applicable electrical codes to ensure compliance. Installation
of this SPD should only be performed by qualified electrical personnel.
All Siemens SPDs are extensively tested in accordance with industry
standards such as ANSI/IEEE C62.41.1, C62.41.2, C62.45, C62.62,
C62.72, UL 1449, UL 1283, IEC 61643, etc.
Warning & Safety Information
This equipment contains hazardous voltages. Death, serious injury,
or property damage can result if safety instructions are not followed.
Only qualified personnel should work on or around this equipment
after becoming thoroughly familiar with all warnings, safety notices,
and maintenance procedures contained herein.
The successful and safe operation of this equipment is dependent upon
proper handling, installation, operation, and maintenance.

Qualified Person

For the purposes of this manual and product labels, a QUALIFIED
PERSON is one who is familiar with the installation, construction, and
operation of this equipment, and the hazards involved. In addition, he
or she has the following qualifications:
(a) Is trained and authorized to energize, deenergize, clear,
ground and tag circuits and equipment in accordance with
established safety practices.
(b) Is trained in the proper care and use of personal protective
equipment (PPE) such as rubber gloves, hard hat, safety
glasses or face shields, flash clothing, etc. in accordance with
established safety practices.
(c) Is trained in rendering first aid.

Danger

For the purposes of this manual and product labels, DANGER indicates
an imminently hazardous situation, which, if not avoided, will result
in death or serious injury.

Notice

For the purposes of this manual and product labels, NOTICE indicates
a potentially hazardous situation which, if not avoided, could result in
damage to the equipment but does not create a potential for personal
injury.
1
These instructions do not purport to cover all details or variations in
equipment, nor to provide for every possible contingency to be met in
connection with installation, operation or maintenance. Should further
information be desired or should particular problems arise which are
not covered sufficiently for the purchaser's purposes, the matter should
be referred to the local Siemens sales office.

Do Not Hi-Pot Test SPDs

Any factory or on-site testing of power distribution equipment that
exceeds normal operating voltage such as high-potential insulation
testing, or any other tests where the suppression components
will be subjected to higher voltage than their rated Maximum
Continuous Operating Voltage (MCOV) must be conducted with
the SPD disconnected from the power source. For 4-wire systems,
the neutral connection at the SPD must also be disconnected prior
to performing high-potential testing and then reconnected after
test completion.
Failure to disconnect SPD and associated components during
elevated voltage testing will damage the SPD and will void the
warranty.

Limited Warranty

Siemens warrants its AC Panel protection products against defective
workmanship and materials for 10 years. Liability is limited to the repair
or replacement of the defective product at Siemens' option. A Return
Material Authorization number (RA#) must be given by the company
prior to the return of any product. Returned products must be sent
to the factory with the transportation charges prepaid. In addition,
the company also warranties unlimited replacement of modular and
component parts within the warranty period previously described.
The company specifically disclaims all other warranties, expressed or
implied. Additionally, the company is not responsible for incidental or
consequential damages resulting from any defect in any product or
component thereof.
The sales contract contains the entire obligation of Siemens. This
instruction manual shall not become part of or modify any prior existing
agreement, commitment or relationship.
Unpacking & Preliminary Inspection
Inspect the entire shipping container for damage or signs of mishandling
before unpacking the unit. Remove the packing material and further
inspect the unit for any obvious shipping damages. If any damage was
found and is a result of shipping or handling, immediately file a claim
with the shipping company and forward a copy to your local Siemens
sales office.

Storage

The unit should be stored in a clean, dry environment. Storage
temperature is -55ºC (-67ºF) to +85ºC (+185ºF). Avoid exposing the
unit to areas of high condensation. All of the packaging materials
should be left intact until the unit is ready for installation. If the unit
has been stored for an extended period of time, it may be necessary
to clean the unit and make a complete inspection of the unit prior to
installing and placing into service.