Initial Start Up For A System With Connection To An Expansion Controller (Pac-Yg50Eca) - Mitsubishi Electric AG-150A Instruction Book

Air-conditioner control system, centralized controller
Hide thumbs Also See for AG-150A:
Table of Contents

Advertisement

5-2 Initial start up for a system with connection to an expansion controller (PAC-YG50ECA)

After the power is turned on, the language selection window will appear.
Select the language to be used for display, and then touch [OK].
Note: It will take approximately 20 seconds for the display to appear after
the power is turned on.
Enter the unit name and ID on the Unit Info window. Set the Expansion
Controller setting to "Use."
(Refer to Section 7-5 for the details on how to set the Name
and Unit ID.)
Touch [Network]
When the unit settings have been completed, touch the right arrow to bring
up the [Network] window, and touch [Network]. Select the [AG-150A] tab,
and set the IP address for the AG-150A.
Select the expansion controller (EC1-EC3) whose settings are to be made
from the tab menu. Check that the DB No. that appears matches that of the
AG-150A. (The DB No. for the AG-150A can be found on the back of the
controller, on the package box, or on the LCD. Refer to Section 7-1 (P 47)
for how to confirm the DB No. on the LCD.)
Touch [
]
If the DB numbers match, make the IP address and M-NET address
settings for each. (Refer to Section 7-6 (P 55) for the details of how to make
the settings.)
* Consult your dealer if the DB numbers do not match.
Touch [Groups]
– 15 –

Advertisement

Table of Contents
loading

Table of Contents