8-2 Night setback function
Night setback function is a function that prevents indoor dew or extreme temperature rise by heating/cooling automatically when the
room temperature goes outside of the specific range during the set time period.
Note: When the air conditioning group with night setback function is off and when the temperature exceeds the preset temperature,
heating/cooling operation starts.
Note: If the room temperature is measured by the air-conditioner's suction temperature sensor, the temperature may not be correct
when the air-conditioner is inactive and the air is not fresh. When the air-conditioner is inactive, using a remote sensor or a
remote control sensor is recommended to measure room temperature correctly.
When the night setback control is set, air conditioning group operates as shown below.
21°C/69°F
Room
temperature
Lower limit
temperature
12°C/53°F
Heating
Heating
On
21°C/69°F
When the temperature drops below the lower limit temperature (heating
8-2-1
Setting of night setback function
To use night setback function, touch [Function 1] on the menu bar on the Initial setting, and then touch [Setback] tab. In this setback
setting window, control time and upper/lower limit temperature for each group can be set.
Note: If the user logs in as a building manager, some of the operations may be prohibited.
Setback control time
setting button
8-2-2
Setting of night setback control time period
To use night setback function, the time period of this control has to be set. Touch [Setback control time period setting] button, then
Setback control window appears as shown below.
Setback setting button
Setback operation stops (when
Setback
the temperature rise 3°C/5.4°F or
operation
the control time period is over)
starts
Heating
Heating
Off
On
Off
12°C/53°F
21°C/69°F
Setback control time period
control)
Upper limit
temperature
28°C/83°F
Room
temperature
24°C/75°F
Cooling
Cooling
On
Off
24°C/75°F
When the temperature rises above the upper limit temperature (cooling
In this window, usability of night setback function and control start/stop
time can be set.
First, touch [Setback setting] button to use night setback function.
Next, set the control time. Set the time by pressing button. After
setting, press OK to reflect the settings. Setback setting window will
be shown. To cancel the setting, touch [Cancel]. Setback setting
window will be shown.
– 77 –
3°C/5.4°F
Setback
Setback
operation
operation
starts
starts
Cooling
Cooling
On
Off
28°C/83°F
24°C/75°F
Setback control time period
control)
Lower/Upper limit
temperature setting
button
Save settings button