Mitsubishi Electric AG-150A Instruction Book page 58

Air-conditioner control system, centralized controller
Hide thumbs Also See for AG-150A:
Table of Contents

Advertisement

• External input settings for a system with connection to an expansion controller (PAC-YG50ECA)
Touch the [Network] tab in the screen that appears when [Initial Settings] on the menu bar in the setting change window is touched to
open the network setting window and make the basic settings for LAN and M-NET.
Note: If the user logs in as a building manager, some of the operations may be prohibited.
Note: When changes are made to the settings, restart the AG-150A before going back to the main menu to reflect the those changes.
* Be sure to make the settings while the expansion controller is connected. (Those settings made without the connection of an expansion
controller will not be reflected.)
If the expansion controller connection setting is set to [Use] (P47), the EC tabs will appear in the Network settings window. Select an EC
from the EC tab menu, and make the settings for the AG-150A and the connected ECs.
First, select [AG-150A] from the EC tab menu, and make the settings for the IP address, subnet mask, and gateway address of the AG-
150A. Refer to 7-6-1 (P 55), 7-6-3 (P 56) for how to make these settings.
* When an expansion controller is connected, the external input/output on the AG-150A will not be available.
IP Address button
Subnet Mask
button
Gateway Address
button
Select the [EC-1], [EC-2], or [EC-3] tab to make the settings for each expansion controller.
IP Address button
Controller setting
(prohibition of local
control)
Before making the settings, check that the DB No. on this window and the DB No. of the AG-150A on the Login window match.
* Consult your dealer if the DB numbers do not match or if the DB No. does not appear.
1. Setting up the expansion controller IP address on the AG-150A
(1) To set up the IP address of each EC, first touch the IP address button to display the keyboard screen. Enter the IP address of the
connected ECs with the keyboard. Use the IP addresses that have been set with the switches on the ECs.
* The controller will not operate properly, if the addresses that are entered here do not match the ones that have been set with the
switches on the ECs.
* Refer to the PAC-YG50ECA expansion controller Installation Manual/Instruction Book for how to set the IP address.
* If the controller does not operate properly, check the settings on the expansion controller and the address settings on the AG-150A.
IP Address button
(2) Press [Save setting] on the network window to save the setting.
– 57 –
EC Tab
M-NET
address input
button
K converter
address input
button
External Input
Setting button

Advertisement

Table of Contents
loading