11 Troubleshooting
Cause and
Assumed cause
correction
When the MC_SyncMoveVelocity
instruction was stopped, the actual
current velocity was not reduced to
10% or less of the maximum velocity
within 10 seconds for three consecu-
tive periods after a command velocity
of 0 was output.
For an OMRON G5-series Servo
Drive, the actual current velocity was
not reduced to 10% or less of the
maximum velocity within 10 seconds
for three consecutive periods when
the MC_TorqueControl instruction
was stopped.
Changing the Control Mode of the
Servo Drive between CSP, CSV, and
CST was not completed within one
second after the command was exe-
cuted.
Attached
None
information
Precautions/
None
Remarks
11-42
Correction
Adjust the commands and load so
that an error does not occur.
Check to see if there is an error in the
Servo Drive and to see if settings are
correct. Correct any problems that are
found.
NJ-series CPU Unit Motion Control User's Manual (W507)
Prevention
Adjust the commands and load so
that an error does not occur.
Make sure that there are no errors in
the Servo Drives and make sure that
the settings are correct.