Field Communicator
Device Dashboard Fast Keys
HART 5 with Diagnostics Fast Keys
HART 7 Fast Keys
Enter the Fast Key sequence "Damping".
AMS Device Manager
1. Right click on the device and select Configure from the menu.
2. Select Manual Setup from the left window pane.
3. In the Process Variables tab, locate Damping and set to desired value.
2.8

LCD display (Optional Order Code)

The LCD display connects directly to the interface/electronics board which maintains direct access to the
signal terminals. The display indicates output and abbreviated diagnostic messages. A display cover is
provided to accommodate the display.
The LCD display features a four-line display and a 0–100% scaled bar graph. The first line of five
characters displays the output description, the second line of seven digits displays the actual value, the
third line of six characters displays engineering units and the fourth line displays "Error" when the
transmitter is in alarm. The LCD display can also display diagnostic messages.
The LCD display configuration command allows customization of the LCD display to suit application
requirements. The LCD display will alternate between the selected items.
Field Communicator
Device Dashboard Fast Keys
HART 5 with Diagnostics Fast Keys
HART 7 Fast Keys
To configure the LCD display, enter the Fast Key sequence.
AMS Device Manager
1. Right click on the device and select Configure from the menu.
2. Select Manual Setup from the left window pane.
3. In the Display tab, select which parameters to show.
2.9

Detailed setup

2.9.1

Failure mode alarm and saturation

Rosemount 3051S Transmitters automatically and continuously perform self-diagnostic routines. If the
self-diagnostic routines detect a failure, the transmitter drives the output to configured alarm values.
Configuration
2, 2, 1, 5
2, 2, 1, 1, 3
2, 2, 1, 1, 3
2, 2, 3
2, 2, 4
2, 2, 4
Configuration
October 2018
29