Eurofast/Minifast Connection - Emerson Rosemount 3051S Series Reference Manual

Scalable pressure, flow, and level solution with hart protocol
Hide thumbs Also See for Rosemount 3051S Series:
Table of Contents

Advertisement

Reference Manual
00809-0100-4801, Rev HA
Figure 3-15. Remote Mount Display Wiring Diagram
Note
Wire colors provided above are per Madison AWM Style 2549 cable. Wire color may vary depending on
cable selected.
Madison AWM Style 2549 cable includes a ground shield. This shield must be connected to earth ground
at either the SuperModule or the Remote Display, but not both.
3.6.5
eurofast
For Rosemount 3051S Transmitters with conduit electrical connectors GE or GM, refer to the cordset
manufacturer's installation instructions for wiring details. For FM Intrinsically Safe, non-incendive or FM
FISCO Intrinsically Safe hazardous locations, install in accordance with Rosemount drawing 03151-1009
to maintain outdoor rating (NEMA
Installation
Junction Box housing
(white) 24 AWG
(blue) 24 AWG
(black) 22 AWG
(red) 22 AWG
®
®
/minifast
connection
®
4X and IP66).
Remote mount display
4-20 mA
Installation
October 2018
65