Installation
October 2018
Reassembly of conduit receptacles
If the conduit receptacle is removed or replaced, follow the instructions below to re-wire the GE or GM
conduit receptacle to the terminal block:
1. Connect the green/yellow lead wire to the internal ground screw.
2. Connect the brown lead wire to the terminal marked (+).
3. Connect the blue lead wire to the terminal marked (pwr/comm-).
3.6.6

Quick Connect wiring

As standard, the Rosemount 3051S Quick Connect arrives properly assembled to the SuperModule and
is ready for installation. Cordsets and field wireable connectors (in shaded area) are sold separately.
Figure 3-16. Quick Connect Exploded View
B
A. Quick Connect housing
B. Straight field wireable connector
C. Right angle field wireable connector
1.
Order part number 03151-9063-0001.
2.
Order part number 03151-9063-0002.
3.
Field wiring supplied by customer.
4.
Supplied by cordset vendor.
Important
If Quick Connect is ordered as a 300S spare housing or is removed from the SuperModule, follow the
instructions below for proper assembly prior to field wiring.
1. Place the Quick Connect onto the SuperModule. To ensure proper pin alignment, remove coupling
nut prior to installing quick Connect onto SuperModule.
2. Place coupling nut over quick connect and wrench tighten to a maximum of 300 in-lb (34 N-m).
3. Tighten the set screw using a
4. Install cordset/field wireable connectors onto the Quick Connect. Do not over tighten.
66
C
D
E
A
F
(1)(3)
(2)(3)
/
-in. hex wrench.
3
32
(4)
D. Cordset
E. Cordset/field wireable coupling nut
F. Quick Connect coupling nut
Reference Manual
00809-0100-4801, Rev HA
Installation