Configuration
October 2018
Selecting burst mode options in HART 7
Message content options:
PV only
Percent of range/current
PV, 2V, 3V, 4V
Process variables and status
Process variables
Device status
All dynamic variables
Selecting a HART 7 trigger mode
When in HART 7 mode, the following trigger modes can be selected.
Continuous (same as HART5 burst mode)
Rising
Falling
Windowed
On change
Note
Consult host system manufacturer for burst mode requirements.
Field Communicator
Device Dashboard Fast Keys
HART 5 with Diagnostics Fast Keys
HART 7 Fast Keys
Enter the Fast Key sequence "Burst Mode" to configure the transmitter for burst mode.
AMS Device Manager
1. Right click on the device and select Configure from the menu.
2. Select Manual Setup from the left window pane.
3. Select the HART tab.
4. Enter the configuration in Burst Mode Configuration fields.
2.12

Multidrop communication

Multidropping transmitters refers to the connection of several transmitters to a single communications
transmission line. Communication between the host and the transmitters takes place digitally with the
analog output of the transmitters deactivated.
Multidrop installation requires consideration of the update rate necessary from each transmitter, the
combination of transmitter models, and the length of the transmission line. Communication with
transmitters can be accomplished with Bell 202 modems and a host implementing HART protocol.
42
2, 2, 4, 3
2, 2, 5, 2
2, 2, 5, 3