Program 116: Initial Commissioning Pb Battery Vented Commercial - Nortec UL60 Operation Manual

Battery charger /analyzer. 0.5 - 40vdc / 0.5 - 60a
Table of Contents

Advertisement

9 Tabular overview of the program procedures
9.2.3

Program 116: Initial commissioning Pb battery vented commercial

16: Pb battery vented commercial
select Batteryprocessing:
P1: Initial commissioning
Enter:
Number of cells
Rated capacity
Step 1:
The message is as follows:
CHECK ELECTROLYTE LEVEL
WAIT 20 MINUTES E=CONTINUE
The program waits at maximum for 20 minutes.
In case the voltage is < 1.5 V for each cell the message is as follows:
U<1.5 V: select program 416
Otherwise:
Discharging with C
until a voltage of 1.5 V for each cell is reached.
5
Step 2:
I-charge with 0.25 C
1
Step 3:
U-charge with 2.4 V × number of cells until charging current is decreased to 0.04 C
End of program
Time monitoring:
I- and U-charge at maximum 8 hours, capacity maximum 1.5 × C
In case inloaded capacity < 0.8 C: failure message: CAPACITY TOO LOW.
60
until a charging voltage of 2.4 V × number of cells is reached.
Initial commissioning
.
1