Program 220: Charge Nicd Battery (Manufacturer Independent) - Nortec UL60 Operation Manual

Battery charger /analyzer. 0.5 - 40vdc / 0.5 - 60a
Table of Contents

Advertisement

9 Tabular overview of the program procedures
9.3.7

Program 220: Charge NiCd battery (manufacturer independent)

20: NiCd battery (manufacturer independent)
select Batteryprocessing:
P2: Charge
Enter:
Number of cells
Rated capacity
Step 1:
Charge with C
until charging voltage of 1.55 V × number of cells is reached.
1
Step 2:
Topping charge C
for 1.5 hours.
5
In case no automatic cell tester is connected:
15 minutens before the end of the topping charge a signal asks for the measurement of the single
cells voltages and to control the electrolyte level.
Otherwise:
15 minutes before the end of the topping charge you are requested to control the electrolyte level.
End of program
Time monitoring:
Charging maximum 90 minutes.
Voltage monitoring:
Monitoring minus ΔU > 30mV/cell during charging, error message:
minus delta U detected
72
Charge