Program 420 Step 4 - Nortec UL60 Operation Manual

Battery charger /analyzer. 0.5 - 40vdc / 0.5 - 60a
Table of Contents

Advertisement

8 Program selection
8.5.4

Program 420 Step 4

NiCd battery (manufacturer independent)
Program:
Maintenance
1
P420:S4: DISCHARGE 2
24.05V
2
5
1
Program number
Kind of treatment
Battery type
2
Step number
3
Step type
4
23:34:38
5
24.05 V
6
4.0 A
7
3.60 Ah
8
0054 MIN
48
04.00A
03.60Ah
6
3
054MIN
7
4 = Maintenance
20 = NiCd battery (manufacturer independent)
= S4
= DISCHARGE 2
= present time
= present battery voltage
= present discharging current
The testing current for NiCd batteries is 1 C (A)
which means a current is chosen which
discharges the battery with a capacity of
A
4
h within 1 hour completely. The current is
4 A.
= actual taken capacity at time of printing.
DISCHARGE 2 the battery will be discharged
with 1 hour current = 4 A until the battery
voltage is 1 V for each cell which means
decreased to 20 V.
The time for discharging until this display is
hown takes 54 minutes.
At the end of step 4 a record is done
automatically when the shut down voltage
of 20 V is reached. The actual voltage recovers
immidiately after stopping discharge current.
The display screen for program 420
15.01.15 23:34:38
--.-°C
8
© Nortec Electronics 2018