9 Tabular overview of the program procedures

9 Tabular overview of the program procedures
The following programs were created with the utmost care according to the maintenance
manuals of the battery manufacturers, but are offered without guarantee. Before applying the
below programmed programs this must be checked for compliance with currently valid main-
tenance manuals of the battery manufacturer. If in doubt or in case of deviations the currently
valid maintenance manual of the battery manufacturer always applies.
For all programs the following restrictions apply:
Sealed lead batteries:
Minimum capacity:
Maximum capacity:
Minimum nominal voltage:
Maximam nominal voltage:
Nominal voltage to be dived by
Vented lead batteries:
Minimum capacity:
Maximum capacity:
Minimum nominal voltage:
Maximum nominal voltage:
Nominal voltage to be dived by
NiCd batteries:
Minimum capacity:
Maximum capacity:
Minimum number of cells:
Maximum number of cells:
Nominal voltage to be dived by
The UL60 can charge / discharge at maximum 60 A. If a battery is connected which usually requires a
higher current it will be charged / discharged with 60 A. The monitored times will be automatically ad-
justed by the program.
In case cables with temperature sensors are used the program shut down will take place under the
following conditions:
Temperature > 65°C
Temperature increase since program start for more than 40°C
© Nortec Electronics 2018
2 Ah
900 Ah
2 V
30 V
2
10 Ah
900 Ah
2 V
30 V
2
1 Ah
230 Ah
1 (nominal voltage: 1.2 V)
24 (nominal voltage: 28.8 V)
1.2
The display screen for program 420
51