9 Tabular overview of the program procedures
9.1.1
Program 000: Discharge (without data specification of a battery)
00: Other battery
select Batteryprocessing:
P0: Discharge
Enter:
Number of cells
Rated capacity
Discharging current
Cut-off voltage per cell
Step 1:
Discharging with discharging current until the cut-off voltage inserted by the user for each cell multi-
plied by the number of cells is reached.
In case no automatic cell tester is connected:
After 48 minutens you get an accustic signal and are asked to measure the single cells.
Otherwise: cell measurement takes place automatically
End of program
Time monitoring:
Discharging maximum 130 minutes.
9.1.2
Program 010: Discharge Pb battery sealed MIL
10: Pb battery sealed MIL
select Batteryprocessing:
P0: Discharge
Enter:
Nominal voltage
Rated capacity
Step 1:
Discharging with C
until a voltage of 1.5 V for each cell is reached.
5
End of program
Example:
A 12 V battery with 100 Ah is connected.
The battery will be discharged with 20 A to 9 V.
Time monitoring:
Discharging maximum 6 hours.
© Nortec Electronics 2018
Discharge
53