Cable entry: top or bottom
Accessibility: Front access only
Walk In/Soft Start: yes
Single input feed is standard. Dual input feed also available upon request.

11.3 Output Characteristics

Output Characteristics
Power, rated:
AC power distribution system: TN-S, TN-C, TN-C-S, TT
available phases
neutral available
Voltage (steady state, r.m.s.), rated:
variation in normal mode / battery mode
Total harmonic distortion (THDu), 100% load, normal mode:
linear
non-linear (according to IEC 62040-3)
Total harmonic distortion, 100 % load, battery mode:
linear
non-linear (according to IEC 62040-3)
Voltage unbalance and phase displacement, 100 % load unbalance
Voltage transient and recovery time, 100% step load:
linear
non-linear (according to IEC 62040-3)
Transfer normal mode --> battery mode
Frequency (steady-state), rated:
Frequency tolerance / variation in normal mode (frq. Synchronized with mains)
Frequency tolerance / variation in battery mode (free-running)
Max synch phase error (referred to a 360° cycle)
Max slew-rate
Nominal current (In), r.m.s. rated:
overload on inverter
Inverter Output Short Circuit Capability
Load power factor, rated
Displacement (permissible lead-lag range)
AC / AC efficiency in normal mode, linear load:
100% load
75% load
50% load
25% load
Eco-mode efficiency, linear load
Crest – Factor (Load supported)
Type: automatic, static switch in each module
transfer time: inverter  bypass / bypass  inverter / in eco-mode
rated current
fault clearing capability (bypass mode) for 20 ms
overload current on bypass mode (< 25°C)
60 Conceptpower DPA 500 480V UL │94-12-043275 A02
UPS Cabinet
Values
500
3
No
3 x 480
± 1.5 / ± 1.5
< 2.0
< 4.0
< 2.0
< 4.0
0
± 4
± 4
0
60
± 2 / ± 4
± 0.1
< 2
1
601
0.5 @ 150% load,
5 @ 125% load,
20 @ 110% load
300% for 100 ms
1.0
(all range) 0
96.0
96.2
96.2
95.3
≥ 99
3:1
Static Bypass
<1 / <5 / <6
666
10xIn
continuously @ 110% load
UPS Module
Unit
Values
100
kW
VAC
%
%
%
°
%
%
%
Hz
%
°
Hz/s
120
A
min
-
-
%, s
%
%
ms
133
A
10xIn
A
min